OpenStudio Results
Model Summary
| Information | Value | Units |
|---|---|---|
| Building Name | NECB 2011-SmallHotel-NECB HDD Method-CAN_BC_Abbotsford.711080_CWEC.epw created: 2017-06-30 16:27:31 +0000 | building_name |
| Net Site Energy | 2,731,723 | kBtu |
| Total Building Area | 43,202 | ft^2 |
| EUI (Based on Net Site Energy and Total Building Area) | 63.23 | kBtu/ft^2 |
| OpenStudio Standards Building Type | SmallHotel |
| Value | |
|---|---|
| Weather File | Abbotsford BC CAN WYEC2-B-24288 WMO#=711080 |
| Latitude | 49.03 |
| Longitude | -122.4 |
| Elevation | 190 (ft) |
| Time Zone | -8.0 |
| North Axis Angle | 180.00 |
| ASHRAE Climate Zone |
| Maximum Dry Bulb (F) | Daily Temperature Range (R) | Humidity Value | Humidity Type | Wind Speed (mph) | Wind Direction | |
|---|---|---|---|---|---|---|
| ABBOTSFORD ANN CLG .4% CONDNS DB=>MWB | 85.28 | 19.98 | 67.1 | Wetbulb [F] | 6.71 | 230.0 |
| ABBOTSFORD ANN CLG .4% CONDNS WB=>MDB | 83.12 | 19.98 | 68.54 | Wetbulb [F] | 6.71 | 230.0 |
| ABBOTSFORD ANN HTG 99.6% CONDNS DB | 16.52 | 0.0 | 16.52 | Wetbulb [F] | 12.3 | 80.0 |
| Time Setpoint Not Met | Time (hr) |
|---|---|
| During Heating | 3.5 |
| During Cooling | 7.0 |
| During Occupied Heating | 3.5 |
| During Occupied Cooling | 7.0 |
| Tolerance for Time Setpoint Not Met | Temperature (F) |
|---|---|
| Heating | 1.8 |
| Cooling | 1.8 |
Annual Overview
| End Use | Consumption (kBtu) |
|---|---|
| Heating | 876,513 |
| Cooling | 56,632 |
| Interior Lighting | 372,615 |
| Exterior Lighting | 0 |
| Interior Equipment | 93,379 |
| Exterior Equipment | 0 |
| Fans | 159,688 |
| Pumps | 23,193 |
| Heat Rejection | 104 |
| Humidification | 0 |
| Heat Recovery | 0 |
| Water Systems | 1,149,598 |
| Refrigeration | 0 |
| Generators | 0 |
| Fuel | Consumption (kBtu) |
|---|---|
| Electricity | 705,612 |
| Natural Gas | 2,026,111 |
| Additional Fuel | 0 |
| District Cooling | 0 |
| District Heating | 0 |
| End Use | Consumption (kWh) |
|---|---|
| Heating | 0 |
| Cooling | 16,597 |
| Interior Lighting | 109,203 |
| Exterior Lighting | 0 |
| Interior Equipment | 27,367 |
| Exterior Equipment | 0 |
| Fans | 46,800 |
| Pumps | 6,797 |
| Heat Rejection | 31 |
| Humidification | 0 |
| Heat Recovery | 0 |
| Water Systems | 0 |
| Refrigeration | 0 |
| Generators | 0 |
| End Use | Consumption (therms) |
|---|---|
| Heating | 8,767 |
| Cooling | 0 |
| Interior Lighting | 0 |
| Exterior Lighting | 0 |
| Interior Equipment | 0 |
| Exterior Equipment | 0 |
| Fans | 0 |
| Pumps | 0 |
| Heat Rejection | 0 |
| Humidification | 0 |
| Heat Recovery | 0 |
| Water Systems | 11,498 |
| Refrigeration | 0 |
| Generators | 0 |
Monthly Overview
| Jan | Feb | Mar | Apr | May | Jun | Jul | Aug | Sep | Oct | Nov | Dec | Total | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Heating | |||||||||||||
| Cooling | 38.52 | 40.57 | 338.02 | 446.47 | 1656.76 | 2437.24 | 4393.56 | 4498.83 | 2007.92 | 652.24 | 74.45 | 13.3 | 16597.88 |
| Interior Lighting | 9274.53 | 8378.94 | 9308.33 | 8924.72 | 9308.33 | 8998.53 | 9234.53 | 9308.33 | 8958.56 | 9274.53 | 8998.53 | 9234.53 | 109202.39 |
| Exterior Lighting | |||||||||||||
| Interior Equipment | 2324.35 | 2099.92 | 2335.12 | 2232.89 | 2335.12 | 2256.72 | 2311.29 | 2335.12 | 2243.66 | 2324.35 | 2256.72 | 2311.29 | 27366.55 |
| Exterior Equipment | |||||||||||||
| Fans | 3586.92 | 3239.06 | 3702.0 | 3607.72 | 4055.58 | 4213.69 | 4691.19 | 4741.83 | 4083.14 | 3822.67 | 3484.14 | 3571.92 | 46799.86 |
| Pumps | 587.47 | 528.99 | 596.09 | 581.63 | 581.55 | 564.55 | 504.37 | 491.57 | 575.48 | 629.85 | 569.35 | 585.5 | 6796.41 |
| Heat Rejection | 0.01 | 0.02 | 0.23 | 0.34 | 1.85 | 3.59 | 9.82 | 9.99 | 5.03 | 0.62 | 0.01 | 0.01 | 31.52 |
| Humidification | |||||||||||||
| Heat Recovery | |||||||||||||
| Water Systems | |||||||||||||
| Refrigeration | |||||||||||||
| Generators | |||||||||||||
| Total | 15811.8 | 14287.49 | 16279.79 | 15793.78 | 17939.18 | 18474.33 | 21144.76 | 21385.68 | 17873.78 | 16704.26 | 15383.19 | 15716.56 | 206794.6 |
| Jan | Feb | Mar | Apr | May | Jun | Jul | Aug | Sep | Oct | Nov | Dec | Total | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Heating | 137.77 | 118.11 | 112.25 | 72.43 | 45.98 | 26.77 | 16.79 | 15.79 | 32.35 | 57.87 | 107.97 | 132.43 | 876.51 |
| Cooling | |||||||||||||
| Interior Lighting | |||||||||||||
| Exterior Lighting | |||||||||||||
| Interior Equipment | |||||||||||||
| Exterior Equipment | |||||||||||||
| Fans | |||||||||||||
| Pumps | |||||||||||||
| Heat Rejection | |||||||||||||
| Humidification | |||||||||||||
| Heat Recovery | |||||||||||||
| Water Systems | 102.95 | 93.77 | 103.11 | 97.37 | 97.81 | 91.62 | 92.24 | 91.58 | 89.39 | 94.53 | 94.58 | 100.65 | 1149.6 |
| Refrigeration | |||||||||||||
| Generators | |||||||||||||
| Total | 240.72 | 211.88 | 215.36 | 169.8 | 143.79 | 118.38 | 109.04 | 107.37 | 121.73 | 152.4 | 202.56 | 233.09 | 2026.11 |
| Jan | Feb | Mar | Apr | May | Jun | Jul | Aug | Sep | Oct | Nov | Dec | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Heating | ||||||||||||
| Cooling | 0.4074 | 0.9056 | 4.3223 | 4.3883 | 7.8996 | 8.7468 | 19.7117 | 10.8043 | 9.4691 | 5.2054 | 2.298 | 0.0833 |
| Interior Lighting | 26.9881 | 26.9881 | 26.9881 | 26.9881 | 26.9881 | 26.9881 | 24.7595 | 26.9881 | 26.9881 | 26.9881 | 26.9881 | 26.9881 |
| Exterior Lighting | ||||||||||||
| Interior Equipment | 6.4671 | 6.4671 | 6.4671 | 6.4671 | 6.4671 | 6.4671 | 5.9441 | 6.4671 | 6.4671 | 6.4671 | 6.4671 | 6.4671 |
| Exterior Equipment | ||||||||||||
| Fans | 5.1431 | 5.353 | 6.743 | 6.7866 | 7.8063 | 7.9619 | 8.9783 | 8.5671 | 8.2276 | 6.8815 | 5.9253 | 5.0516 |
| Pumps | 0.778 | 0.778 | 0.9731 | 0.9731 | 0.9731 | 0.9731 | 0.2138 | 0.9731 | 0.9731 | 0.9731 | 0.778 | 0.9731 |
| Heat Rejection | 0.0049 | 0.0713 | 0.0141 | 0.012 | ||||||||
| Humidification | ||||||||||||
| Heat Recovery | ||||||||||||
| Water Systems | ||||||||||||
| Refrigeration | ||||||||||||
| Generators | ||||||||||||
| Total | 39.78 | 40.49 | 45.49 | 45.6 | 50.13 | 51.14 | 59.68 | 53.81 | 52.14 | 46.52 | 42.46 | 39.56 |
| Jan | Feb | Mar | Apr | May | Jun | Jul | Aug | Sep | Oct | Nov | Dec | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Heating | 385.0124 | 448.6137 | 482.5087 | 305.9244 | 183.5634 | 98.4517 | 62.4519 | 77.1448 | 119.9339 | 225.0013 | 391.2697 | 380.4458 |
| Cooling | ||||||||||||
| Interior Lighting | ||||||||||||
| Exterior Lighting | ||||||||||||
| Interior Equipment | ||||||||||||
| Exterior Equipment | ||||||||||||
| Fans | ||||||||||||
| Pumps | ||||||||||||
| Heat Rejection | ||||||||||||
| Humidification | ||||||||||||
| Heat Recovery | ||||||||||||
| Water Systems | 282.5802 | 285.8612 | 243.8463 | 246.6015 | 249.9627 | 237.0046 | 239.7266 | 194.644 | 233.1312 | 246.5786 | 236.1542 | 275.8698 |
| Refrigeration | ||||||||||||
| Generators | ||||||||||||
| Total | 667.59 | 734.47 | 726.35 | 552.53 | 433.53 | 335.46 | 302.18 | 271.79 | 353.07 | 471.58 | 627.42 | 656.32 |
Utility Bills/Rates
No Data to Show for Utility Bills/Rates
Envelope
| Construction | Net Area (ft^2) | Surface Count | R Value (ft^2*h*R/Btu) |
|---|---|---|---|
| Customized opaque construction {5175ba3f-35bf-4c5a-9bd7-dcd350485e6d} to conductance of 0.315 | 16,258 | 92 | 18.03 |
| Customized opaque construction {e9da9745-2c33-4bd8-b5bb-21148b5c4c49} to conductance of 0.227 | 10,800 | 16 | 25.01 |
| Construction | Area (ft^2) | Surface Count | U-Factor (Btu/ft^2*h*R) |
|---|---|---|---|
| Customized Fenestration: cond=0.240 tvis=0.220 tsol=0.232 | 1,983 | 103 | 0.4227 |
| Description | Total (%) | North (%) | East (%) | South (%) | West (%) |
|---|---|---|---|---|---|
| Gross Window-Wall Ratio | 10.87 | 15.24 | 3.95 | 11.39 | 3.13 |
| Gross Window-Wall Ratio (Conditioned) | 10.87 | 15.24 | 3.95 | 11.39 | 3.13 |
| Skylight-Roof Ratio | 0.0 |
Space Type Breakdown
| Space Type Name | Floor Area (ft^2) | Standards Building Type | Standards Space Type |
|---|---|---|---|
| Space Function Corr. >= 2.4m wide-sch-F | 5,670 | Space Function | Corr. >= 2.4m wide-sch-F |
| Space Function Electrical/Mechanical-sch-F | 1,215 | Space Function | Electrical/Mechanical-sch-F |
| Space Function Gym - fitness | 351 | Space Function | Gym - fitness |
| Space Function Hotel/Motel - lobby | 1,755 | Space Function | Hotel/Motel - lobby |
| Space Function Hway lodging - rooms | 27,271 | Space Function | Hway lodging - rooms |
| Space Function Lobby - elevator | 648 | Space Function | Lobby - elevator |
| Space Function Lounge/recreation | 351 | Space Function | Lounge/recreation |
| Space Function Office - enclosed | 1,404 | Space Function | Office - enclosed |
| Space Function Stairway-sch-F | 1,728 | Space Function | Stairway-sch-F |
| Space Function Storage area - occsens | 2,457 | Space Function | Storage area - occsens |
| Space Function Washroom-sch-F | 351 | Space Function | Washroom-sch-F |
Space Type Summary
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Corr. >= 2.4m wide-sch-F People Definition | 0.0009 | people/ft^2 | 1.0 |
| Space Function Corr. >= 2.4m wide-sch-F Lights Definition | 0.6596 | W/ft^2 | 1.0 |
| Space Function Corr. >= 2.4m wide-sch-F Ventilation (outdoor air method Sum) | 0.0600 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Electrical/Mechanical-sch-F People Definition | 0.0005 | people/ft^2 | 1.0 |
| Space Function Electrical/Mechanical-sch-F Elec Equip Definition | 0.0929 | W/ft^2 | 1.0 |
| Space Function Electrical/Mechanical-sch-F Lights Definition | 1.2356 | W/ft^2 | 1.0 |
| Space Function Electrical/Mechanical-sch-F Ventilation (outdoor air method Sum) | 0.0600 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Gym - fitness People Definition | 0.0186 | people/ft^2 | 1.0 |
| Space Function Gym - fitness Elec Equip Definition | 0.0929 | W/ft^2 | 1.0 |
| Space Function Gym - fitness Lights Definition | 0.9104 | W/ft^2 | 1.0 |
| Space Function Gym - fitness Ventilation (outdoor air method Sum) | 0.8600 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Hotel/Motel - lobby People Definition | 0.0093 | people/ft^2 | 1.0 |
| Space Function Hotel/Motel - lobby Elec Equip Definition | 0.2323 | W/ft^2 | 1.0 |
| Space Function Hotel/Motel - lobby Lights Definition | 1.0591 | W/ft^2 | 1.0 |
| Space Function Hotel/Motel - lobby Ventilation (outdoor air method Sum) | 0.2850 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Hway lodging - rooms People Definition | 0.0037 | people/ft^2 | 1.0 |
| Space Function Hway lodging - rooms Elec Equip Definition | 0.2323 | W/ft^2 | 1.0 |
| Space Function Hway lodging - rooms Lights Definition | 0.7525 | W/ft^2 | 1.0 |
| Space Function Hway lodging - rooms Ventilation (outdoor air method Sum) | 0.1100 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Lobby - elevator People Definition | 0.0093 | people/ft^2 | 1.0 |
| Space Function Lobby - elevator Elec Equip Definition | 0.0929 | W/ft^2 | 1.0 |
| Space Function Lobby - elevator Lights Definition | 0.6410 | W/ft^2 | 1.0 |
| Space Function Lobby - elevator Ventilation (outdoor air method Sum) | 0.8100 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Lounge/recreation People Definition | 0.0093 | people/ft^2 | 1.0 |
| Space Function Lounge/recreation Elec Equip Definition | 0.0929 | W/ft^2 | 1.0 |
| Space Function Lounge/recreation Lights Definition | 0.7860 | W/ft^2 | 1.0 |
| Space Function Lounge/recreation Ventilation (outdoor air method Sum) | 0.1850 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Office - enclosed People Definition | 0.0046 | people/ft^2 | 1.0 |
| Space Function Office - enclosed Elec Equip Definition | 0.6968 | W/ft^2 | 1.0 |
| Space Function Office - enclosed Lights Definition | 1.1055 | W/ft^2 | 1.0 |
| Space Function Office - enclosed Ventilation (outdoor air method Sum) | 0.0850 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Stairway-sch-F People Definition | 0.0005 | people/ft^2 | 1.0 |
| Space Function Stairway-sch-F Lights Definition | 0.6875 | W/ft^2 | 1.0 |
| Space Function Stairway-sch-F Ventilation (outdoor air method Sum) | 0.0600 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Storage area - occsens People Definition | 0.0009 | people/ft^2 | 1.0 |
| Space Function Storage area - occsens Elec Equip Definition | 0.0929 | W/ft^2 | 1.0 |
| Space Function Storage area - occsens Lights Definition | 0.5686 | W/ft^2 | 1.0 |
| Space Function Storage area - occsens Ventilation (outdoor air method Sum) | 0.0700 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Washroom-sch-F People Definition | 0.0031 | people/ft^2 | 1.0 |
| Space Function Washroom-sch-F Elec Equip Definition | 0.0929 | W/ft^2 | 1.0 |
| Space Function Washroom-sch-F Lights Definition | 0.8779 | W/ft^2 | 1.0 |
| Space Function Washroom-sch-F Ventilation (outdoor air method Sum) | 0.0600 | cfm/floor area ft^2 |
Interior Lighting Summary
| Zone | Lighting Power Density (W/ft^2) | Total Power (W) | Schedule Name | Scheduled Hours/Week (hr) | Actual Load Hours/Week (hr) | Return Air Fraction | Annual Consumption (kWh) | |
|---|---|---|---|---|---|---|---|---|
| SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION CORR. >= 2.4M WIDE-SCH-F LIGHTS | SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.66 | 1068.58 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3180.56 |
| SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION CORR. >= 2.4M WIDE-SCH-F LIGHTS | SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.66 | 890.48 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 2650.0 |
| SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION CORR. >= 2.4M WIDE-SCH-F LIGHTS | SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.66 | 890.48 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 2650.0 |
| SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION CORR. >= 2.4M WIDE-SCH-F LIGHTS | SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.66 | 890.48 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 2650.0 |
| SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION ELECTRICAL/MECHANICAL-SCH-F LIGHTS | SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 1.24 | 433.73 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 1291.67 |
| SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION ELECTRICAL/MECHANICAL-SCH-F LIGHTS | SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 1.24 | 1067.63 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3177.78 |
| SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN SPACE FUNCTION GYM - FITNESS LIGHTS | SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | 0.91 | 319.57 | NECB-B-LIGHTING | 103.58 | 103.57 | 0.0000 | 1725.0 |
| SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN SPACE FUNCTION HOTEL/MOTEL - LOBBY LIGHTS | SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | 1.06 | 1858.83 | NECB-H-LIGHTING | 151.2 | 151.2 | 0.0000 | 14655.56 |
| SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0.75 | 1056.6 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0.75 | 853.41 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 2541.67 |
| SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0.75 | 1056.6 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1056.52 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1056.52 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0.75 | 1056.6 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0.75 | 853.41 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 2541.67 |
| SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0.75 | 1056.6 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1056.52 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1056.52 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 0.75 | 1056.6 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 0.75 | 853.41 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 2541.67 |
| SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 0.75 | 1056.6 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1056.52 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1056.52 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN SPACE FUNCTION LOBBY - ELEVATOR LIGHTS | SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | 0.64 | 103.85 | NECB-C-LIGHTING | 75.0 | 75.0 | 0.0000 | 405.56 |
| SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN SPACE FUNCTION LOBBY - ELEVATOR LIGHTS | SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | 0.64 | 103.85 | NECB-C-LIGHTING | 75.0 | 75.0 | 0.0000 | 405.56 |
| SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN SPACE FUNCTION LOBBY - ELEVATOR LIGHTS | SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | 0.64 | 103.85 | NECB-C-LIGHTING | 75.0 | 75.0 | 0.0000 | 405.56 |
| SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN SPACE FUNCTION LOBBY - ELEVATOR LIGHTS | SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | 0.64 | 103.85 | NECB-C-LIGHTING | 75.0 | 75.0 | 0.0000 | 405.56 |
| SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN SPACE FUNCTION LOUNGE/RECREATION LIGHTS | SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | 0.79 | 275.87 | NECB-B-LIGHTING | 103.58 | 103.57 | 0.0000 | 1488.89 |
| SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN SPACE FUNCTION OFFICE - ENCLOSED LIGHTS | SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | 1.11 | 1552.17 | NECB-A-LIGHTING | 56.27 | 56.27 | 0.0000 | 4552.78 |
| SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN | 0.69 | 148.49 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN | 0.69 | 148.49 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN | 0.69 | 148.49 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN | 0.69 | 148.49 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN | 0.69 | 148.53 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN | 0.69 | 148.53 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN | 0.69 | 148.53 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN | 0.69 | 148.53 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 0.57 | 76.76 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 219.44 |
| SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | 0.57 | 76.76 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 219.44 |
| SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | 0.57 | 76.76 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 219.44 |
| SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | 0.57 | 76.76 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 219.44 |
| SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 0.57 | 598.7 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 1711.11 |
| SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | 0.57 | 122.85 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 350.0 |
| SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | 0.57 | 122.85 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 350.0 |
| SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | 0.57 | 122.85 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 350.0 |
| SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | 0.57 | 122.85 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 350.0 |
| SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION WASHROOM-SCH-F LIGHTS | SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.88 | 308.17 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 916.67 |
Plug Loads Summary
| Electricity Annual Value (kWh) | |
|---|---|
| InteriorEquipment:Electricity:Zone:SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 97.22 |
| InteriorEquipment:Electricity:Zone:SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 238.89 |
| InteriorEquipment:Electricity:Zone:SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | 175.0 |
| InteriorEquipment:Electricity:Zone:SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | 3213.89 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 783.33 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 783.33 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 783.33 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | 175.0 |
| InteriorEquipment:Electricity:Zone:SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | 3622.22 |
| InteriorEquipment:Electricity:Zone:SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 36.11 |
| InteriorEquipment:Electricity:Zone:SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | 36.11 |
| InteriorEquipment:Electricity:Zone:SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | 36.11 |
| InteriorEquipment:Electricity:Zone:SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | 36.11 |
| InteriorEquipment:Electricity:Zone:SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 280.56 |
| InteriorEquipment:Electricity:Zone:SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 97.22 |
Exterior Lighting
No Data to Show for Exterior Lighting
Water Use Equipment
| Instance | Plant Loop | Definition | Space | Peak Flow Rate (gal/min) | Flow Rate Schedule | Target Temp Range (F) |
|---|---|---|---|---|---|---|
| Employeeloungeflr1 Service Water Use 0.02gal/min | Main Service Water Loop | Employeeloungeflr1 Service Water Use Def 0.02gal/min | EmployeeLoungeFlr1 | 0.02 | NECB-B-Service Water Heating | 140.0 to 140.0 |
| Exercisecenterflr1 Service Water Use 0.05gal/min | Main Service Water Loop | Exercisecenterflr1 Service Water Use Def 0.05gal/min | ExerciseCenterFlr1 | 0.05 | NECB-B-Service Water Heating | 140.0 to 140.0 |
| Frontloungeflr1 Service Water Use 0.04gal/min | Main Service Water Loop | Frontloungeflr1 Service Water Use Def 0.04gal/min | FrontLoungeFlr1 | 0.04 | NECB-H-Service Water Heating | 140.0 to 140.0 |
| Frontofficeflr1 Service Water Use 0.05gal/min | Main Service Water Loop | Frontofficeflr1 Service Water Use Def 0.05gal/min | FrontOfficeFlr1 | 0.05 | NECB-A-Service Water Heating | 140.0 to 140.0 |
| Frontstorageflr1 Service Water Use 0.0gal/min | Main Service Water Loop | Frontstorageflr1 Service Water Use Def 0.0gal/min | FrontStorageFlr1 | 0.00 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Frontstorageflr2 Service Water Use 0.0gal/min | Main Service Water Loop | Frontstorageflr2 Service Water Use Def 0.0gal/min | FrontStorageFlr2 | 0.00 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Frontstorageflr3 Service Water Use 0.0gal/min | Main Service Water Loop | Frontstorageflr3 Service Water Use Def 0.0gal/min | FrontStorageFlr3 | 0.00 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Frontstorageflr4 Service Water Use 0.0gal/min | Main Service Water Loop | Frontstorageflr4 Service Water Use Def 0.0gal/min | FrontStorageFlr4 | 0.00 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Guestroom101 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom101 Service Water Use Def 0.07gal/min | GuestRoom101 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom102 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom102 Service Water Use Def 0.07gal/min | GuestRoom102 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom103 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom103 Service Water Use Def 0.07gal/min | GuestRoom103 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom104 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom104 Service Water Use Def 0.07gal/min | GuestRoom104 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom105 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom105 Service Water Use Def 0.07gal/min | GuestRoom105 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom201 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom201 Service Water Use Def 0.07gal/min | GuestRoom201 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom202_205 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom202_205 Service Water Use Def 0.27gal/min | GuestRoom202_205 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom206_208 Service Water Use 0.22gal/min | Main Service Water Loop | Guestroom206_208 Service Water Use Def 0.22gal/min | GuestRoom206_208 | 0.22 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom209_212 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom209_212 Service Water Use Def 0.27gal/min | GuestRoom209_212 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom213 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom213 Service Water Use Def 0.07gal/min | GuestRoom213 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom214 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom214 Service Water Use Def 0.07gal/min | GuestRoom214 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom215_218 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom215_218 Service Water Use Def 0.27gal/min | GuestRoom215_218 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom219 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom219 Service Water Use Def 0.07gal/min | GuestRoom219 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom220_223 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom220_223 Service Water Use Def 0.27gal/min | GuestRoom220_223 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom224 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom224 Service Water Use Def 0.07gal/min | GuestRoom224 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom301 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom301 Service Water Use Def 0.07gal/min | GuestRoom301 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom302_305 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom302_305 Service Water Use Def 0.27gal/min | GuestRoom302_305 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom306_308 Service Water Use 0.22gal/min | Main Service Water Loop | Guestroom306_308 Service Water Use Def 0.22gal/min | GuestRoom306_308 | 0.22 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom309_312 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom309_312 Service Water Use Def 0.27gal/min | GuestRoom309_312 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom313 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom313 Service Water Use Def 0.07gal/min | GuestRoom313 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom314 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom314 Service Water Use Def 0.07gal/min | GuestRoom314 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom315_318 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom315_318 Service Water Use Def 0.27gal/min | GuestRoom315_318 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom319 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom319 Service Water Use Def 0.07gal/min | GuestRoom319 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom320_323 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom320_323 Service Water Use Def 0.27gal/min | GuestRoom320_323 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom324 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom324 Service Water Use Def 0.07gal/min | GuestRoom324 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom401 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom401 Service Water Use Def 0.07gal/min | GuestRoom401 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom402_405 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom402_405 Service Water Use Def 0.27gal/min | GuestRoom402_405 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom406_408 Service Water Use 0.22gal/min | Main Service Water Loop | Guestroom406_408 Service Water Use Def 0.22gal/min | GuestRoom406_408 | 0.22 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom409_412 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom409_412 Service Water Use Def 0.27gal/min | GuestRoom409_412 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom413 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom413 Service Water Use Def 0.07gal/min | GuestRoom413 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom414 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom414 Service Water Use Def 0.07gal/min | GuestRoom414 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom415_418 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom415_418 Service Water Use Def 0.27gal/min | GuestRoom415_418 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom419 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom419 Service Water Use Def 0.07gal/min | GuestRoom419 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom420_423 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom420_423 Service Water Use Def 0.27gal/min | GuestRoom420_423 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom424 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom424 Service Water Use Def 0.07gal/min | GuestRoom424 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Laundryroomflr1 Service Water Use 0.03gal/min | Main Service Water Loop | Laundryroomflr1 Service Water Use Def 0.03gal/min | LaundryRoomFlr1 | 0.03 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Rearstorageflr1 Service Water Use 0.01gal/min | Main Service Water Loop | Rearstorageflr1 Service Water Use Def 0.01gal/min | RearStorageFlr1 | 0.01 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Rearstorageflr2 Service Water Use 0.01gal/min | Main Service Water Loop | Rearstorageflr2 Service Water Use Def 0.01gal/min | RearStorageFlr2 | 0.01 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Rearstorageflr3 Service Water Use 0.01gal/min | Main Service Water Loop | Rearstorageflr3 Service Water Use Def 0.01gal/min | RearStorageFlr3 | 0.01 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Rearstorageflr4 Service Water Use 0.01gal/min | Main Service Water Loop | Rearstorageflr4 Service Water Use Def 0.01gal/min | RearStorageFlr4 | 0.01 | NECB-E-Service Water Heating | 140.0 to 140.0 |
HVAC Load Profiles
| Jan | Feb | Mar | Apr | May | Jun | Jul | Aug | Sep | Oct | Nov | Dec | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Average Outdoor Air Dry Bulb (F) | 37.1 | 39.0 | 41.8 | 47.2 | 54.1 | 57.8 | 62.3 | 62.8 | 56.3 | 50.3 | 41.5 | 38.3 |
| Cooling Load (MBtu) | 0.13 | 0.14 | 1.15 | 1.52 | 5.65 | 8.32 | 14.99 | 15.35 | 6.85 | 2.23 | 0.25 | 0.05 |
| Heating Load (MBtu) | 137.77 | 118.11 | 112.25 | 72.43 | 45.98 | 26.77 | 16.79 | 15.79 | 32.35 | 57.87 | 107.97 | 132.43 |
Zone Conditions
| Zone | Unmet Htg (hr) | Unmet Htg - Occ (hr) | < 56 (F) | 56-61 (F) | 61-66 (F) | 66-68 (F) | 68-70 (F) | 70-72 (F) | 72-74 (F) | 74-76 (F) | 76-78 (F) | 78-83 (F) | 83-88 (F) | >= 88 (F) | Unmet Clg (hr) | Unmet Clg - Occ (hr) | Mean Temp (F) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 190 | 832 | 3541 | 1500 | 2697 | 0 | 0 | 0 | 0 | 0 | 0 | 72.5 (F) |
| SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 2184 | 2219 | 4357 | 0 | 0 | 0 | 0 | 0 | 0 | 73.5 (F) |
| SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 15 | 2547 | 1882 | 4316 | 0 | 0 | 0 | 0 | 0 | 0 | 73.5 (F) |
| SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 73 | 372 | 606 | 3255 | 1609 | 2845 | 0 | 0 | 0 | 0 | 0 | 0 | 72.4 (F) |
| SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 2463 | 905 | 717 | 3728 | 394 | 553 | 0 | 0 | 0 | 0 | 0 | 0 | 69.2 (F) |
| SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 2190 | 1283 | 623 | 3768 | 376 | 520 | 0 | 0 | 0 | 0 | 0 | 0 | 69.3 (F) |
| SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 2201 | 1284 | 609 | 3763 | 379 | 524 | 0 | 0 | 0 | 0 | 0 | 0 | 69.3 (F) |
| SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 3032 | 828 | 279 | 3608 | 367 | 646 | 0 | 0 | 0 | 0 | 0 | 0 | 69.0 (F) |
| SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 414 | 730 | 642 | 3627 | 1256 | 2088 | 3 | 0 | 0 | 0 | 0 | 0 | 71.7 (F) |
| SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | 3 | 3 | 0 | 0 | 0 | 94 | 207 | 2345 | 2903 | 2843 | 359 | 9 | 0 | 0 | 0 | 0 | 73.2 (F) |
| SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 19 | 995 | 4340 | 1284 | 2095 | 27 | 0 | 0 | 0 | 7 | 7 | 72.3 (F) |
| SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 102 | 716 | 1764 | 2167 | 3736 | 275 | 0 | 0 | 0 | 0 | 0 | 73.2 (F) |
| SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN | 0 | 0 | 0 | 0 | 205 | 527 | 634 | 4082 | 1112 | 2200 | 0 | 0 | 0 | 0 | 0 | 0 | 72.0 (F) |
| SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN | 0 | 0 | 0 | 0 | 110 | 520 | 637 | 4001 | 1136 | 2356 | 0 | 0 | 0 | 0 | 0 | 0 | 72.1 (F) |
| SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN | 0 | 0 | 0 | 0 | 154 | 507 | 626 | 3961 | 1112 | 2400 | 0 | 0 | 0 | 0 | 0 | 0 | 72.1 (F) |
| SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN | 0 | 0 | 0 | 0 | 667 | 344 | 531 | 4010 | 880 | 2328 | 0 | 0 | 0 | 0 | 0 | 0 | 71.8 (F) |
| SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 15 | 651 | 1651 | 2362 | 1552 | 2421 | 108 | 0 | 0 | 0 | 0 | 0 | 71.9 (F) |
| SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 356 | 1626 | 2480 | 1570 | 2610 | 115 | 3 | 0 | 0 | 0 | 0 | 72.2 (F) |
| SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 5 | 461 | 1618 | 2423 | 1487 | 2599 | 160 | 7 | 0 | 0 | 0 | 0 | 72.2 (F) |
| SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 555 | 1040 | 1137 | 2318 | 1218 | 2256 | 206 | 30 | 0 | 0 | 0 | 0 | 71.5 (F) |
| SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 23 | 2190 | 2402 | 4145 | 0 | 0 | 0 | 0 | 0 | 0 | 73.4 (F) |
| SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 24 | 2282 | 2310 | 4144 | 0 | 0 | 0 | 0 | 0 | 0 | 73.4 (F) |
| SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 263 | 2855 | 2028 | 3614 | 0 | 0 | 0 | 0 | 0 | 0 | 73.1 (F) |
| SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 17 | 1604 | 2468 | 4663 | 8 | 0 | 0 | 0 | 0 | 0 | 73.6 (F) |
| SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 10 | 1395 | 2389 | 4964 | 2 | 0 | 0 | 0 | 0 | 0 | 73.8 (F) |
| SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | 0 | 0 | 0 | 0 | 0 | 17 | 164 | 2618 | 1698 | 4263 | 0 | 0 | 0 | 0 | 0 | 0 | 73.3 (F) |
| SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 7 | 815 | 2477 | 5461 | 0 | 0 | 0 | 0 | 0 | 0 | 73.9 (F) |
| SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 12 | 1401 | 2387 | 4960 | 0 | 0 | 0 | 0 | 0 | 0 | 73.7 (F) |
| SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 12 | 1271 | 2437 | 5040 | 0 | 0 | 0 | 0 | 0 | 0 | 73.8 (F) |
| SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 64 | 2443 | 1968 | 4285 | 0 | 0 | 0 | 0 | 0 | 0 | 73.4 (F) |
| SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 873 | 2374 | 5513 | 0 | 0 | 0 | 0 | 0 | 0 | 74.0 (F) |
| SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 674 | 2200 | 5886 | 0 | 0 | 0 | 0 | 0 | 0 | 74.1 (F) |
| SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 12 | 1410 | 2424 | 4914 | 0 | 0 | 0 | 0 | 0 | 0 | 73.7 (F) |
| SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 379 | 1999 | 6382 | 0 | 0 | 0 | 0 | 0 | 0 | 74.2 (F) |
| SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 673 | 2265 | 5822 | 0 | 0 | 0 | 0 | 0 | 0 | 74.1 (F) |
| SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | 0 | 0 | 0 | 0 | 8 | 25 | 436 | 2854 | 1529 | 3908 | 0 | 0 | 0 | 0 | 0 | 0 | 73.0 (F) |
| SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 19 | 1578 | 2180 | 4983 | 0 | 0 | 0 | 0 | 0 | 0 | 73.7 (F) |
| SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 25 | 1861 | 1994 | 4880 | 0 | 0 | 0 | 0 | 0 | 0 | 73.6 (F) |
| SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 22 | 1739 | 2086 | 4913 | 0 | 0 | 0 | 0 | 0 | 0 | 73.6 (F) |
| SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 134 | 2653 | 1770 | 4203 | 0 | 0 | 0 | 0 | 0 | 0 | 73.3 (F) |
| SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 7 | 1209 | 2263 | 5281 | 0 | 0 | 0 | 0 | 0 | 0 | 73.8 (F) |
| SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 783 | 2098 | 5878 | 1 | 0 | 0 | 0 | 0 | 0 | 74.0 (F) |
| SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 15 | 1456 | 2337 | 4952 | 0 | 0 | 0 | 0 | 0 | 0 | 73.7 (F) |
| SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 637 | 2116 | 6007 | 0 | 0 | 0 | 0 | 0 | 0 | 74.1 (F) |
| SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 2 | 1089 | 2278 | 5391 | 0 | 0 | 0 | 0 | 0 | 0 | 73.9 (F) |
| SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | 1 | 1 | 0 | 0 | 248 | 439 | 480 | 3391 | 1269 | 2933 | 0 | 0 | 0 | 0 | 0 | 0 | 72.2 (F) |
| SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 1 | 1 | 0 | 0 | 69 | 272 | 554 | 2839 | 1548 | 3478 | 0 | 0 | 0 | 0 | 0 | 0 | 72.7 (F) |
| SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 76 | 287 | 561 | 2864 | 1503 | 3469 | 0 | 0 | 0 | 0 | 0 | 0 | 72.6 (F) |
| SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 70 | 273 | 561 | 2845 | 1544 | 3467 | 0 | 0 | 0 | 0 | 0 | 0 | 72.6 (F) |
| SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 99 | 431 | 569 | 3205 | 1341 | 3115 | 0 | 0 | 0 | 0 | 0 | 0 | 72.4 (F) |
| SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 51 | 246 | 565 | 2612 | 1625 | 3657 | 4 | 0 | 0 | 0 | 0 | 0 | 72.8 (F) |
| SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 50 | 189 | 529 | 2358 | 1630 | 3993 | 11 | 0 | 0 | 0 | 0 | 0 | 72.9 (F) |
| SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 50 | 280 | 661 | 2753 | 1814 | 3198 | 4 | 0 | 0 | 0 | 0 | 0 | 72.6 (F) |
| SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 48 | 183 | 517 | 2351 | 1634 | 4016 | 11 | 0 | 0 | 0 | 0 | 0 | 73.0 (F) |
| SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 48 | 236 | 588 | 2577 | 1592 | 3713 | 6 | 0 | 0 | 0 | 0 | 0 | 72.8 (F) |
| SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 580 | 1308 | 1006 | 2383 | 1582 | 1793 | 90 | 18 | 0 | 0 | 0 | 0 | 71.2 (F) |
| SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 182 | 787 | 3477 | 1453 | 2861 | 0 | 0 | 0 | 0 | 0 | 0 | 72.6 (F) |
| SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 15 | 510 | 696 | 3632 | 1333 | 2574 | 0 | 0 | 0 | 0 | 0 | 0 | 72.3 (F) |
| SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN | 0 | 0 | 0 | 0 | 15 | 231 | 757 | 3897 | 1615 | 2245 | 0 | 0 | 0 | 0 | 0 | 0 | 72.3 (F) |
| SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN | 0 | 0 | 0 | 0 | 10 | 113 | 726 | 3686 | 1608 | 2617 | 0 | 0 | 0 | 0 | 0 | 0 | 72.5 (F) |
| SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN | 0 | 0 | 0 | 0 | 16 | 177 | 725 | 3744 | 1539 | 2559 | 0 | 0 | 0 | 0 | 0 | 0 | 72.4 (F) |
| SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN | 1 | 1 | 0 | 0 | 472 | 489 | 460 | 4038 | 1338 | 1963 | 0 | 0 | 0 | 0 | 0 | 0 | 71.7 (F) |
| SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | 0 | 0 | 0 | 0 | 1097 | 982 | 852 | 2548 | 1112 | 1959 | 205 | 5 | 0 | 0 | 0 | 0 | 71.0 (F) |
| SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | 0 | 0 | 0 | 0 | 993 | 987 | 831 | 2485 | 1140 | 2067 | 245 | 12 | 0 | 0 | 0 | 0 | 71.2 (F) |
| SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | 0 | 0 | 0 | 0 | 1137 | 886 | 815 | 2446 | 1121 | 2044 | 293 | 18 | 0 | 0 | 0 | 0 | 71.1 (F) |
| SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | 0 | 0 | 0 | 0 | 1928 | 588 | 768 | 2339 | 938 | 1920 | 226 | 50 | 3 | 0 | 0 | 0 | 70.6 (F) |
| SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 43 | 735 | 3461 | 1388 | 3133 | 0 | 0 | 0 | 0 | 0 | 0 | 72.8 (F) |
| Zone | < 30 (%) | 30-35 (%) | 35-40 (%) | 40-45 (%) | 45-50 (%) | 50-55 (%) | 55-60 (%) | 60-65 (%) | 65-70 (%) | 70-75 (%) | 75-80 (%) | >= 80 (%) | Mean Relative Humidity (%) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 2669 | 1721 | 1115 | 1515 | 1254 | 395 | 91 | 0 | 0 | 0 | 0 | 0 | 35.4 (%) |
| SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 3237 | 1560 | 1102 | 1375 | 1087 | 334 | 65 | 0 | 0 | 0 | 0 | 0 | 34.3 (%) |
| SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 3193 | 1589 | 1099 | 1370 | 1087 | 349 | 73 | 0 | 0 | 0 | 0 | 0 | 34.4 (%) |
| SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 2858 | 1633 | 1085 | 1217 | 1300 | 519 | 129 | 19 | 0 | 0 | 0 | 0 | 35.4 (%) |
| SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | 2230 | 1443 | 1107 | 776 | 837 | 1014 | 872 | 363 | 113 | 5 | 0 | 0 | 39.5 (%) |
| SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | 2267 | 1457 | 1081 | 777 | 803 | 993 | 883 | 379 | 112 | 8 | 0 | 0 | 39.4 (%) |
| SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | 2267 | 1461 | 1079 | 781 | 801 | 986 | 885 | 379 | 113 | 8 | 0 | 0 | 39.4 (%) |
| SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | 2229 | 1414 | 1102 | 781 | 831 | 921 | 855 | 446 | 151 | 30 | 0 | 0 | 39.8 (%) |
| SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | 1241 | 1269 | 1446 | 1250 | 1458 | 1188 | 659 | 221 | 28 | 0 | 0 | 0 | 41.5 (%) |
| SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | 166 | 239 | 562 | 907 | 1096 | 1381 | 1995 | 1037 | 747 | 289 | 183 | 158 | 54.2 (%) |
| SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | 1009 | 1181 | 1727 | 1103 | 1192 | 1393 | 888 | 247 | 20 | 0 | 0 | 0 | 42.5 (%) |
| SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | 1707 | 1470 | 1489 | 2314 | 1194 | 578 | 8 | 0 | 0 | 0 | 0 | 0 | 37.6 (%) |
| SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN | 2871 | 1554 | 1073 | 1279 | 1261 | 573 | 144 | 5 | 0 | 0 | 0 | 0 | 35.4 (%) |
| SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN | 2947 | 1544 | 1105 | 1316 | 1182 | 537 | 124 | 5 | 0 | 0 | 0 | 0 | 35.2 (%) |
| SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN | 2950 | 1534 | 1124 | 1338 | 1185 | 500 | 124 | 5 | 0 | 0 | 0 | 0 | 35.1 (%) |
| SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN | 2843 | 1486 | 1195 | 1437 | 1202 | 475 | 110 | 9 | 3 | 0 | 0 | 0 | 35.3 (%) |
| SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 2122 | 1682 | 1348 | 1468 | 1394 | 620 | 112 | 14 | 0 | 0 | 0 | 0 | 37.0 (%) |
| SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | 2312 | 1596 | 1345 | 1411 | 1289 | 647 | 140 | 20 | 0 | 0 | 0 | 0 | 36.7 (%) |
| SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | 2284 | 1619 | 1360 | 1401 | 1310 | 627 | 145 | 14 | 0 | 0 | 0 | 0 | 36.7 (%) |
| SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | 2075 | 1778 | 1347 | 1463 | 1411 | 530 | 133 | 23 | 0 | 0 | 0 | 0 | 36.9 (%) |
| SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 80 | 176 | 460 | 1140 | 2071 | 2027 | 1737 | 874 | 187 | 8 | 0 | 0 | 50.9 (%) |
| SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 80 | 174 | 461 | 1127 | 2061 | 2016 | 1748 | 887 | 197 | 9 | 0 | 0 | 51.0 (%) |
| SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 77 | 161 | 422 | 1043 | 1919 | 2030 | 1833 | 993 | 268 | 14 | 0 | 0 | 51.6 (%) |
| SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 98 | 214 | 538 | 1224 | 2084 | 1989 | 1693 | 743 | 167 | 10 | 0 | 0 | 50.3 (%) |
| SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 108 | 234 | 570 | 1298 | 2082 | 2105 | 1591 | 636 | 130 | 6 | 0 | 0 | 49.9 (%) |
| SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | 210 | 270 | 788 | 1741 | 2086 | 1934 | 1287 | 393 | 51 | 0 | 0 | 0 | 48.0 (%) |
| SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 138 | 259 | 739 | 1797 | 2163 | 1912 | 1307 | 405 | 40 | 0 | 0 | 0 | 48.2 (%) |
| SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 132 | 237 | 676 | 1675 | 2153 | 1914 | 1401 | 486 | 86 | 0 | 0 | 0 | 48.8 (%) |
| SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 132 | 242 | 690 | 1687 | 2131 | 1863 | 1412 | 507 | 96 | 0 | 0 | 0 | 48.8 (%) |
| SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 122 | 221 | 599 | 1491 | 2135 | 2039 | 1487 | 568 | 97 | 1 | 0 | 0 | 49.4 (%) |
| SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 166 | 304 | 801 | 1750 | 2094 | 1903 | 1288 | 394 | 60 | 0 | 0 | 0 | 48.0 (%) |
| SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 176 | 325 | 847 | 1756 | 2051 | 1811 | 1306 | 430 | 58 | 0 | 0 | 0 | 47.9 (%) |
| SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 148 | 273 | 697 | 1602 | 2020 | 1817 | 1449 | 607 | 144 | 3 | 0 | 0 | 49.0 (%) |
| SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 188 | 351 | 962 | 1854 | 1990 | 1814 | 1212 | 347 | 42 | 0 | 0 | 0 | 47.4 (%) |
| SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 168 | 322 | 836 | 1827 | 2060 | 1940 | 1229 | 339 | 39 | 0 | 0 | 0 | 47.7 (%) |
| SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | 211 | 271 | 756 | 1671 | 2005 | 1841 | 1386 | 517 | 101 | 1 | 0 | 0 | 48.4 (%) |
| SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 135 | 245 | 692 | 1702 | 2156 | 1887 | 1382 | 478 | 83 | 0 | 0 | 0 | 48.6 (%) |
| SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 131 | 239 | 677 | 1661 | 2167 | 1911 | 1406 | 475 | 93 | 0 | 0 | 0 | 48.8 (%) |
| SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 131 | 243 | 678 | 1672 | 2148 | 1895 | 1401 | 494 | 98 | 0 | 0 | 0 | 48.8 (%) |
| SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 125 | 218 | 599 | 1476 | 2137 | 2036 | 1496 | 571 | 101 | 1 | 0 | 0 | 49.4 (%) |
| SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 155 | 294 | 792 | 1743 | 2117 | 1914 | 1283 | 398 | 64 | 0 | 0 | 0 | 48.1 (%) |
| SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 180 | 334 | 883 | 1810 | 2029 | 1845 | 1255 | 370 | 54 | 0 | 0 | 0 | 47.7 (%) |
| SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 152 | 283 | 724 | 1615 | 2019 | 1832 | 1411 | 574 | 145 | 5 | 0 | 0 | 48.9 (%) |
| SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 183 | 338 | 901 | 1843 | 2031 | 1844 | 1227 | 346 | 47 | 0 | 0 | 0 | 47.6 (%) |
| SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 157 | 298 | 797 | 1766 | 2121 | 1935 | 1271 | 370 | 45 | 0 | 0 | 0 | 48.0 (%) |
| SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | 291 | 343 | 868 | 1703 | 1789 | 1666 | 1365 | 576 | 154 | 5 | 0 | 0 | 48.0 (%) |
| SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 233 | 297 | 780 | 1729 | 1935 | 1716 | 1402 | 524 | 139 | 5 | 0 | 0 | 48.3 (%) |
| SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 231 | 298 | 783 | 1707 | 1966 | 1729 | 1384 | 519 | 138 | 5 | 0 | 0 | 48.3 (%) |
| SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 233 | 297 | 780 | 1718 | 1937 | 1715 | 1405 | 529 | 141 | 5 | 0 | 0 | 48.4 (%) |
| SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 230 | 282 | 711 | 1639 | 1913 | 1781 | 1417 | 625 | 158 | 4 | 0 | 0 | 48.7 (%) |
| SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 253 | 342 | 824 | 1749 | 1928 | 1706 | 1299 | 514 | 142 | 3 | 0 | 0 | 48.0 (%) |
| SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 264 | 360 | 880 | 1804 | 1911 | 1661 | 1276 | 482 | 121 | 1 | 0 | 0 | 47.7 (%) |
| SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 253 | 333 | 788 | 1703 | 1871 | 1584 | 1296 | 705 | 202 | 25 | 0 | 0 | 48.5 (%) |
| SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 263 | 361 | 883 | 1805 | 1918 | 1668 | 1272 | 475 | 114 | 1 | 0 | 0 | 47.7 (%) |
| SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 253 | 347 | 816 | 1772 | 1938 | 1710 | 1285 | 511 | 126 | 2 | 0 | 0 | 47.9 (%) |
| SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 1836 | 1595 | 1478 | 1310 | 1454 | 819 | 227 | 40 | 1 | 0 | 0 | 0 | 38.1 (%) |
| SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 3061 | 1558 | 1166 | 1471 | 1076 | 349 | 79 | 0 | 0 | 0 | 0 | 0 | 34.6 (%) |
| SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 2931 | 1576 | 1149 | 1498 | 1128 | 393 | 85 | 0 | 0 | 0 | 0 | 0 | 34.9 (%) |
| SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN | 3084 | 1495 | 1071 | 1164 | 1164 | 587 | 173 | 22 | 0 | 0 | 0 | 0 | 35.1 (%) |
| SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN | 3190 | 1473 | 1086 | 1175 | 1143 | 523 | 153 | 17 | 0 | 0 | 0 | 0 | 34.8 (%) |
| SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN | 3168 | 1479 | 1084 | 1168 | 1152 | 525 | 160 | 24 | 0 | 0 | 0 | 0 | 34.9 (%) |
| SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN | 2930 | 1493 | 1096 | 1101 | 1293 | 604 | 199 | 39 | 5 | 0 | 0 | 0 | 35.6 (%) |
| SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | 1820 | 1725 | 1464 | 1383 | 1385 | 733 | 222 | 28 | 0 | 0 | 0 | 0 | 37.8 (%) |
| SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | 1920 | 1723 | 1447 | 1434 | 1346 | 669 | 200 | 21 | 0 | 0 | 0 | 0 | 37.5 (%) |
| SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | 1909 | 1738 | 1455 | 1414 | 1367 | 657 | 200 | 20 | 0 | 0 | 0 | 0 | 37.5 (%) |
| SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | 1859 | 1600 | 1478 | 1439 | 1505 | 654 | 200 | 20 | 5 | 0 | 0 | 0 | 37.8 (%) |
| SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 1601 | 1557 | 1557 | 1193 | 1752 | 872 | 218 | 10 | 0 | 0 | 0 | 0 | 38.8 (%) |
Zone Overview
| Area (ft^2) | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume (ft^3) | Multiplier | Above Ground Gross Wall Area (ft^2) | Underground Gross Wall Area (ft^2) | Window Glass Area (ft^2) | Lighting (W/ft^2) | People (ft^2/person) | Plug and Process (W/ft^2) | |
|---|---|---|---|---|---|---|---|---|---|---|---|
| SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 1620.08 | Yes | Yes | 17820.49 | 1.00 | 351.98 | 0.0 | 105.7 | 0.66 | 1075.31 | 0.0 |
| SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 1350.01 | Yes | Yes | 12150.01 | 1.00 | 197.95 | 0.0 | 28.2 | 0.66 | 1075.31 | 0.0 |
| SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 1350.01 | Yes | Yes | 12150.01 | 1.00 | 197.95 | 0.0 | 28.2 | 0.66 | 1075.31 | 0.0 |
| SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 1350.01 | Yes | Yes | 12150.01 | 1.00 | 197.95 | 0.0 | 28.2 | 0.66 | 1075.31 | 0.0 |
| SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | 162.0 | Yes | Yes | 1781.98 | 1.00 | 65.98 | 0.0 | 0.0 | 0.64 | 107.64 | 0.09 |
| SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | 162.0 | Yes | Yes | 1458.14 | 1.00 | 54.03 | 0.0 | 0.0 | 0.64 | 107.64 | 0.09 |
| SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | 162.0 | Yes | Yes | 1458.14 | 1.00 | 54.03 | 0.0 | 0.0 | 0.64 | 107.64 | 0.09 |
| SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | 162.0 | Yes | Yes | 1458.14 | 1.00 | 54.03 | 0.0 | 0.0 | 0.64 | 107.64 | 0.09 |
| SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3860.95 | 1.00 | 143.05 | 0.0 | 17.76 | 0.79 | 107.64 | 0.09 |
| SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3860.95 | 1.00 | 143.05 | 0.0 | 17.76 | 0.91 | 53.82 | 0.09 |
| SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | 1755.16 | Yes | Yes | 19306.53 | 1.00 | 1012.02 | 0.0 | 159.63 | 1.06 | 107.64 | 0.23 |
| SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | 1404.04 | Yes | Yes | 15444.16 | 1.00 | 571.99 | 0.0 | 70.83 | 1.11 | 215.06 | 0.7 |
| SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN | 216.03 | Yes | Yes | 2375.97 | 1.00 | 385.03 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN | 216.03 | Yes | Yes | 1944.07 | 1.00 | 314.95 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN | 216.03 | Yes | Yes | 1944.07 | 1.00 | 314.95 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN | 216.03 | Yes | Yes | 1944.07 | 1.00 | 314.95 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 134.98 | Yes | Yes | 1484.98 | 1.00 | 55.0 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | 134.98 | Yes | Yes | 1214.82 | 1.00 | 44.99 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | 134.98 | Yes | Yes | 1214.82 | 1.00 | 44.99 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | 134.98 | Yes | Yes | 1214.82 | 1.00 | 44.99 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3861.31 | 1.00 | 143.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3861.31 | 1.00 | 143.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3861.31 | 1.00 | 143.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3860.95 | 1.00 | 143.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3860.95 | 1.00 | 143.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 360.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 1134.09 | Yes | Yes | 10206.64 | 1.00 | 378.03 | 0.0 | 72.12 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 360.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 1134.09 | Yes | Yes | 10206.64 | 1.00 | 378.03 | 0.0 | 72.12 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 360.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 1134.09 | Yes | Yes | 10206.64 | 1.00 | 378.03 | 0.0 | 72.12 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 1053.03 | Yes | Yes | 11582.86 | 1.00 | 429.05 | 0.0 | 53.17 | 0.57 | 1075.31 | 0.09 |
| SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3861.31 | 1.00 | 143.05 | 0.0 | 0.0 | 1.24 | 2173.88 | 0.09 |
| SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 864.02 | Yes | Yes | 9504.59 | 1.00 | 351.98 | 0.0 | 53.17 | 1.24 | 2173.88 | 0.09 |
| SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN | 216.03 | Yes | Yes | 2376.68 | 1.00 | 385.03 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN | 216.03 | Yes | Yes | 1944.43 | 1.00 | 315.06 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN | 216.03 | Yes | Yes | 1944.43 | 1.00 | 315.06 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN | 216.03 | Yes | Yes | 1944.43 | 1.00 | 315.06 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | 216.03 | Yes | Yes | 2376.68 | 1.00 | 385.03 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | 216.03 | Yes | Yes | 1944.78 | 1.00 | 315.06 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | 216.03 | Yes | Yes | 1944.78 | 1.00 | 315.06 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | 216.03 | Yes | Yes | 1944.78 | 1.00 | 315.06 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3861.31 | 1.00 | 143.05 | 0.0 | 0.0 | 0.88 | 322.59 | 0.09 |
| Total | 43201.82 | 410417.54 | 18240.31 | 0.0 | 1982.71 | 0.77 | 287.83 | 0.19 | |||
| Conditioned Total | 43201.82 | 410417.54 | 18240.31 | 0.0 | 1982.71 | 0.77 | 287.83 | 0.19 | |||
| Unconditioned Total | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | |||
| Not Part of Total | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
| Heating/Cooling | Calculated Design Load | Design Load With Sizing Factor | Calculated Design Air Flow (ft^3/min) | Design Air Flow With Sizing Factor (ft^3/min) | Date/Time Of Peak | Outdoor Temperature at Peak Load (F) | Outdoor Humidity Ratio at Peak Load (lbWater/lbAir) | |
|---|---|---|---|---|---|---|---|---|
| SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Cooling | 0.41 (ton) | 0.45 (ton) | 228.84 | 252.15 | 7/21 17:00:00 | 82.49 | 0.01 |
| SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Heating | 6.83 (kBtu/h) | 8.87 (kBtu/h) | 161.03 | 209.77 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.32 (ton) | 0.35 (ton) | 175.87 | 192.82 | 7/21 22:00:00 | 71.69 | 0.01 |
| SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Heating | 3.41 (kBtu/h) | 4.44 (kBtu/h) | 80.52 | 105.94 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.33 (ton) | 0.36 (ton) | 182.22 | 201.29 | 7/21 22:00:00 | 71.69 | 0.01 |
| SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Heating | 5.05 (kBtu/h) | 6.57 (kBtu/h) | 120.78 | 156.8 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.56 (ton) | 0.61 (ton) | 309.36 | 341.14 | 7/21 14:45:00 | 85.28 | 0.01 |
| SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Heating | 14.14 (kBtu/h) | 18.39 (kBtu/h) | 339.02 | 440.73 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | Cooling | 0.06 (ton) | 0.07 (ton) | 33.9 | 131.37 | 7/21 17:00:00 | 82.49 | 0.01 |
| SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | Heating | 0.91 (kBtu/h) | 1.18 (kBtu/h) | 21.19 | 131.37 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | Cooling | 0.06 (ton) | 0.06 (ton) | 31.78 | 131.37 | 7/21 17:00:00 | 82.49 | 0.01 |
| SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | Heating | 0.63 (kBtu/h) | 0.82 (kBtu/h) | 14.83 | 131.37 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | Cooling | 0.06 (ton) | 0.07 (ton) | 33.9 | 131.37 | 7/21 17:00:00 | 82.49 | 0.01 |
| SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | Heating | 0.79 (kBtu/h) | 1.03 (kBtu/h) | 19.07 | 131.37 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | Cooling | 0.09 (ton) | 0.1 (ton) | 50.85 | 131.37 | 7/21 14:15:00 | 85.28 | 0.01 |
| SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | Heating | 1.96 (kBtu/h) | 2.55 (kBtu/h) | 46.62 | 131.37 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | Cooling | 0.18 (ton) | 0.19 (ton) | 97.47 | 108.06 | 7/21 13:15:00 | 84.52 | 0.01 |
| SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | Heating | 1.15 (kBtu/h) | 1.49 (kBtu/h) | 27.55 | 65.69 | 12/21 10:00:00 | 16.52 | 0.0 |
| SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | Cooling | 0.23 (ton) | 0.26 (ton) | 131.37 | 300.88 | 7/21 13:00:00 | 84.29 | 0.01 |
| SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | Heating | 1.02 (kBtu/h) | 1.33 (kBtu/h) | 23.31 | 300.88 | 12/21 10:00:00 | 16.52 | 0.0 |
| SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | Cooling | 0.83 (ton) | 0.91 (ton) | 461.92 | 506.41 | 7/21 19:30:00 | 76.39 | 0.01 |
| SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | Heating | 0.0 (kBtu/h) | 0.0 (kBtu/h) | 0.0 | 500.06 | 16.52 | 0.0 | |
| SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | Cooling | 0.75 (ton) | 0.82 (ton) | 415.3 | 457.68 | 7/21 12:15:00 | 83.08 | 0.01 |
| SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | Heating | 3.68 (kBtu/h) | 4.78 (kBtu/h) | 84.76 | 118.66 | 12/21 08:00:00 | 16.52 | 0.0 |
| SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN | Cooling | 0.05 (ton) | 0.05 (ton) | 27.55 | 29.66 | 7/21 22:00:00 | 71.69 | 0.01 |
| SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN | Heating | 2.67 (kBtu/h) | 3.47 (kBtu/h) | 63.57 | 82.64 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN | Cooling | 0.05 (ton) | 0.06 (ton) | 27.55 | 31.78 | 7/21 22:00:00 | 71.69 | 0.01 |
| SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN | Heating | 2.33 (kBtu/h) | 3.03 (kBtu/h) | 55.09 | 72.04 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN | Cooling | 0.05 (ton) | 0.06 (ton) | 29.66 | 33.9 | 7/21 22:00:00 | 71.69 | 0.01 |
| SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN | Heating | 2.56 (kBtu/h) | 3.32 (kBtu/h) | 61.45 | 80.52 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN | Cooling | 0.08 (ton) | 0.09 (ton) | 44.5 | 48.73 | 7/21 14:30:00 | 85.28 | 0.01 |
| SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN | Heating | 3.75 (kBtu/h) | 4.87 (kBtu/h) | 88.99 | 116.54 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | Cooling | 0.04 (ton) | 0.05 (ton) | 23.31 | 25.43 | 7/21 14:00:00 | 85.28 | 0.01 |
| SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | Heating | 0.99 (kBtu/h) | 1.28 (kBtu/h) | 23.31 | 29.66 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | Cooling | 0.04 (ton) | 0.04 (ton) | 19.07 | 21.19 | 7/21 14:00:00 | 85.28 | 0.01 |
| SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | Heating | 0.81 (kBtu/h) | 1.06 (kBtu/h) | 19.07 | 25.43 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | Cooling | 0.04 (ton) | 0.04 (ton) | 19.07 | 21.19 | 7/21 16:00:00 | 84.07 | 0.01 |
| SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | Heating | 0.98 (kBtu/h) | 1.28 (kBtu/h) | 23.31 | 29.66 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | Cooling | 0.07 (ton) | 0.07 (ton) | 36.02 | 40.26 | 7/21 14:00:00 | 85.28 | 0.01 |
| SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | Heating | 1.92 (kBtu/h) | 2.5 (kBtu/h) | 46.62 | 59.33 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | Cooling | 0.08 (ton) | 0.09 (ton) | 46.62 | 50.85 | 7/21 22:00:00 | 71.69 | 0.01 |
| SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | Heating | 1.29 (kBtu/h) | 1.67 (kBtu/h) | 29.66 | 40.26 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | Cooling | 0.08 (ton) | 0.09 (ton) | 46.62 | 50.85 | 7/21 22:00:00 | 71.69 | 0.01 |
| SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | Heating | 1.38 (kBtu/h) | 1.79 (kBtu/h) | 31.78 | 42.38 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | Cooling | 0.08 (ton) | 0.09 (ton) | 46.62 | 50.85 | 7/21 22:00:00 | 71.69 | 0.01 |
| SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | Heating | 1.69 (kBtu/h) | 2.2 (kBtu/h) | 40.26 | 52.97 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.09 (ton) | 0.1 (ton) | 50.85 | 55.09 | 7/21 22:00:00 | 71.69 | 0.01 |
| SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | Heating | 1.6 (kBtu/h) | 2.07 (kBtu/h) | 38.14 | 48.73 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.1 (ton) | 0.11 (ton) | 55.09 | 61.45 | 7/21 13:15:00 | 84.52 | 0.01 |
| SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | Heating | 1.46 (kBtu/h) | 1.89 (kBtu/h) | 33.9 | 44.5 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | Cooling | 0.12 (ton) | 0.13 (ton) | 67.8 | 74.16 | 7/21 22:00:00 | 71.69 | 0.01 |
| SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | Heating | 2.2 (kBtu/h) | 2.86 (kBtu/h) | 52.97 | 67.8 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Cooling | 0.4 (ton) | 0.44 (ton) | 220.36 | 241.55 | 7/21 22:00:00 | 71.69 | 0.01 |
| SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Heating | 2.67 (kBtu/h) | 3.47 (kBtu/h) | 63.57 | 154.68 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Cooling | 0.29 (ton) | 0.32 (ton) | 158.92 | 175.87 | 7/21 22:00:00 | 71.69 | 0.01 |
| SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Heating | 3.02 (kBtu/h) | 3.93 (kBtu/h) | 72.04 | 125.01 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Cooling | 0.34 (ton) | 0.37 (ton) | 188.58 | 207.65 | 7/21 22:00:00 | 71.69 | 0.01 |
| SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Heating | 3.46 (kBtu/h) | 4.49 (kBtu/h) | 82.64 | 154.68 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Cooling | 0.09 (ton) | 0.1 (ton) | 52.97 | 57.21 | 7/21 22:00:00 | 71.69 | 0.01 |
| SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Heating | 1.4 (kBtu/h) | 1.82 (kBtu/h) | 33.9 | 42.38 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.1 (ton) | 0.11 (ton) | 57.21 | 61.45 | 7/21 22:00:00 | 71.69 | 0.01 |
| SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Heating | 1.26 (kBtu/h) | 1.64 (kBtu/h) | 29.66 | 38.14 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.39 (ton) | 0.43 (ton) | 218.24 | 239.43 | 7/21 22:00:00 | 71.69 | 0.01 |
| SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Heating | 3.76 (kBtu/h) | 4.89 (kBtu/h) | 88.99 | 154.68 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.1 (ton) | 0.12 (ton) | 57.21 | 63.57 | 7/21 22:00:00 | 71.69 | 0.01 |
| SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Heating | 1.1 (kBtu/h) | 1.43 (kBtu/h) | 25.43 | 38.14 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.41 (ton) | 0.45 (ton) | 228.84 | 252.15 | 7/21 22:00:00 | 71.69 | 0.01 |
| SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Heating | 3.25 (kBtu/h) | 4.22 (kBtu/h) | 76.28 | 154.68 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.11 (ton) | 0.12 (ton) | 61.45 | 67.8 | 7/21 22:00:00 | 71.69 | 0.01 |
| SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Heating | 1.03 (kBtu/h) | 1.34 (kBtu/h) | 25.43 | 38.14 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | Cooling | 0.12 (ton) | 0.13 (ton) | 63.57 | 69.92 | 7/21 22:00:00 | 71.69 | 0.01 |
| SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | Heating | 2.89 (kBtu/h) | 3.76 (kBtu/h) | 69.92 | 88.99 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Cooling | 0.38 (ton) | 0.42 (ton) | 211.89 | 230.96 | 7/21 22:00:00 | 71.69 | 0.01 |
| SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Heating | 4.87 (kBtu/h) | 6.33 (kBtu/h) | 114.42 | 154.68 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Cooling | 0.31 (ton) | 0.34 (ton) | 169.51 | 188.58 | 7/21 22:00:00 | 71.69 | 0.01 |
| SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Heating | 4.15 (kBtu/h) | 5.39 (kBtu/h) | 97.47 | 127.13 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Cooling | 0.37 (ton) | 0.4 (ton) | 203.41 | 224.6 | 7/21 22:00:00 | 71.69 | 0.01 |
| SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Heating | 4.89 (kBtu/h) | 6.36 (kBtu/h) | 116.54 | 154.68 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Cooling | 0.1 (ton) | 0.11 (ton) | 55.09 | 61.45 | 7/21 22:00:00 | 71.69 | 0.01 |
| SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Heating | 1.66 (kBtu/h) | 2.15 (kBtu/h) | 40.26 | 50.85 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.11 (ton) | 0.12 (ton) | 59.33 | 65.69 | 7/21 22:00:00 | 71.69 | 0.01 |
| SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Heating | 1.54 (kBtu/h) | 2.01 (kBtu/h) | 36.02 | 48.73 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.41 (ton) | 0.45 (ton) | 228.84 | 252.15 | 7/21 22:00:00 | 71.69 | 0.01 |
| SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Heating | 4.9 (kBtu/h) | 6.37 (kBtu/h) | 116.54 | 154.68 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.11 (ton) | 0.12 (ton) | 59.33 | 65.69 | 7/21 22:00:00 | 71.69 | 0.01 |
| SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Heating | 1.39 (kBtu/h) | 1.8 (kBtu/h) | 33.9 | 42.38 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.41 (ton) | 0.46 (ton) | 228.84 | 252.15 | 7/21 22:00:00 | 71.69 | 0.01 |
| SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Heating | 4.81 (kBtu/h) | 6.25 (kBtu/h) | 114.42 | 154.68 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.11 (ton) | 0.12 (ton) | 59.33 | 65.69 | 7/21 22:00:00 | 71.69 | 0.01 |
| SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Heating | 1.44 (kBtu/h) | 1.87 (kBtu/h) | 33.9 | 44.5 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | Cooling | 0.15 (ton) | 0.17 (ton) | 82.64 | 91.11 | 7/21 14:15:00 | 85.28 | 0.01 |
| SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | Heating | 4.77 (kBtu/h) | 6.2 (kBtu/h) | 114.42 | 148.32 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Cooling | 0.48 (ton) | 0.53 (ton) | 266.98 | 294.52 | 7/21 12:15:00 | 83.08 | 0.01 |
| SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Heating | 11.77 (kBtu/h) | 15.31 (kBtu/h) | 281.81 | 366.57 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Cooling | 0.41 (ton) | 0.45 (ton) | 224.6 | 247.91 | 7/21 13:45:00 | 85.03 | 0.01 |
| SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Heating | 9.81 (kBtu/h) | 12.76 (kBtu/h) | 235.2 | 305.12 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Cooling | 0.48 (ton) | 0.52 (ton) | 264.86 | 290.29 | 7/21 12:15:00 | 83.08 | 0.01 |
| SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Heating | 11.74 (kBtu/h) | 15.27 (kBtu/h) | 281.81 | 364.45 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Cooling | 0.13 (ton) | 0.14 (ton) | 72.04 | 78.4 | 7/21 13:45:00 | 85.03 | 0.01 |
| SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Heating | 3.6 (kBtu/h) | 4.69 (kBtu/h) | 86.87 | 112.3 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.18 (ton) | 0.19 (ton) | 97.47 | 105.94 | 7/21 13:15:00 | 84.52 | 0.01 |
| SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Heating | 3.54 (kBtu/h) | 4.6 (kBtu/h) | 84.76 | 110.18 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.68 (ton) | 0.74 (ton) | 375.04 | 413.18 | 7/21 12:45:00 | 83.88 | 0.01 |
| SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Heating | 11.72 (kBtu/h) | 15.24 (kBtu/h) | 279.69 | 364.45 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.18 (ton) | 0.19 (ton) | 97.47 | 108.06 | 7/21 13:15:00 | 84.52 | 0.01 |
| SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Heating | 3.43 (kBtu/h) | 4.46 (kBtu/h) | 82.64 | 105.94 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.67 (ton) | 0.74 (ton) | 370.8 | 408.94 | 7/21 12:45:00 | 83.88 | 0.01 |
| SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Heating | 11.67 (kBtu/h) | 15.17 (kBtu/h) | 279.69 | 362.33 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.17 (ton) | 0.19 (ton) | 97.47 | 105.94 | 7/21 13:15:00 | 84.52 | 0.01 |
| SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Heating | 3.47 (kBtu/h) | 4.51 (kBtu/h) | 82.64 | 108.06 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | Cooling | 0.32 (ton) | 0.35 (ton) | 177.99 | 197.06 | 7/21 13:15:00 | 84.52 | 0.01 |
| SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | Heating | 5.0 (kBtu/h) | 6.5 (kBtu/h) | 118.66 | 154.68 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Cooling | 0.09 (ton) | 0.1 (ton) | 48.73 | 52.97 | 7/21 22:00:00 | 71.69 | 0.01 |
| SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Heating | 1.17 (kBtu/h) | 1.52 (kBtu/h) | 27.55 | 36.02 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Cooling | 0.2 (ton) | 0.22 (ton) | 110.18 | 120.78 | 7/21 22:00:00 | 71.69 | 0.01 |
| SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Heating | 3.18 (kBtu/h) | 4.13 (kBtu/h) | 74.16 | 97.47 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN | Cooling | 0.05 (ton) | 0.06 (ton) | 29.66 | 31.78 | 7/21 22:15:00 | 71.35 | 0.01 |
| SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN | Heating | 2.63 (kBtu/h) | 3.42 (kBtu/h) | 63.57 | 82.64 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN | Cooling | 0.05 (ton) | 0.06 (ton) | 29.66 | 31.78 | 7/21 22:00:00 | 71.69 | 0.01 |
| SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN | Heating | 2.28 (kBtu/h) | 2.96 (kBtu/h) | 55.09 | 69.92 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN | Cooling | 0.06 (ton) | 0.06 (ton) | 31.78 | 33.9 | 7/21 22:00:00 | 71.69 | 0.01 |
| SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN | Heating | 2.5 (kBtu/h) | 3.25 (kBtu/h) | 59.33 | 78.4 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN | Cooling | 0.08 (ton) | 0.09 (ton) | 44.5 | 48.73 | 7/21 14:00:00 | 85.28 | 0.01 |
| SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN | Heating | 3.72 (kBtu/h) | 4.84 (kBtu/h) | 88.99 | 116.54 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | Cooling | 0.05 (ton) | 0.06 (ton) | 29.66 | 31.78 | 7/21 18:00:00 | 80.49 | 0.01 |
| SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | Heating | 2.96 (kBtu/h) | 3.84 (kBtu/h) | 69.92 | 91.11 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | Cooling | 0.06 (ton) | 0.06 (ton) | 31.78 | 33.9 | 7/21 14:00:00 | 85.28 | 0.01 |
| SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | Heating | 2.66 (kBtu/h) | 3.45 (kBtu/h) | 63.57 | 82.64 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | Cooling | 0.06 (ton) | 0.07 (ton) | 33.9 | 36.02 | 7/21 16:00:00 | 84.07 | 0.01 |
| SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | Heating | 2.89 (kBtu/h) | 3.75 (kBtu/h) | 69.92 | 91.11 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | Cooling | 0.1 (ton) | 0.11 (ton) | 55.09 | 61.45 | 7/21 14:00:00 | 85.28 | 0.01 |
| SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | Heating | 3.9 (kBtu/h) | 5.07 (kBtu/h) | 93.23 | 122.9 | 12/21 09:00:00 | 16.52 | 0.0 |
| SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Cooling | 0.09 (ton) | 0.1 (ton) | 48.73 | 55.09 | 7/21 22:00:00 | 71.69 | 0.01 |
| SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Heating | 0.72 (kBtu/h) | 0.94 (kBtu/h) | 16.95 | 23.31 | 12/21 09:00:00 | 16.52 | 0.0 |
Zone Equipment Detail
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
Air Loops Detail
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.35 | COP | |
| OS:Coil:Heating:Water | Autosized | gal/min | Plant Loop | Hot Water Loop | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:Scheduled | Control Variable - Temperature | 68.0 to 68.0 | F | |||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 32,185 | ft^2 | 42 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 42 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Make-up air unit Occ Sch | |||||
| Night Cycle Setting | CycleOnAny | Choice | ||||
| Economizer Setting | DifferentialEnthalpy | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-CorridorFlr1 Sys-3 Flr-2 Sch-F HPlcmt-north ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 1,620 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-ElevatorCoreFlr1 Sys-3 Flr-2 Sch-C HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 162 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-ElevatorCoreFlr2 Sys-3 Flr-1 Sch-C HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 162 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-ElevatorCoreFlr3 Sys-3 Flr-4 Sch-C HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 162 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-ElevatorCoreFlr4 Sys-3 Flr-3 Sch-C HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 162 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-EmployeeLoungeFlr1 Sys-3 Flr-2 Sch-B HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 351 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontLoungeFlr1 Sys-3 Flr-2 Sch-H HPlcmt-north ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 1,755 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStairsFlr1 Sys-4 Flr-2 Sch-F HPlcmt-east ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStairsFlr2 Sys-4 Flr-1 Sch-F HPlcmt-east ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStairsFlr3 Sys-4 Flr-4 Sch-F HPlcmt-east ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStairsFlr4 Sys-4 Flr-3 Sch-F HPlcmt-east ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStorageFlr1 Sys-4 Flr-2 Sch-E HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 135 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStorageFlr2 Sys-4 Flr-1 Sch-E HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 135 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStorageFlr3 Sys-4 Flr-4 Sch-E HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 135 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStorageFlr4 Sys-4 Flr-3 Sch-E HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 135 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-LaundryRoomFlr1 Sys-4 Flr-2 Sch-E HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 1,053 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-MechanicalRoomFlr1 Sys-3 Flr-2 Sch-F HPlcmt-north ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 351 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-MeetingRoomFlr1 Sys-3 Flr-2 Sch-F HPlcmt-north ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 864 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-RearStorageFlr1 Sys-4 Flr-2 Sch-E HPlcmt-west ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-RearStorageFlr2 Sys-4 Flr-1 Sch-E HPlcmt-west ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-RearStorageFlr3 Sys-4 Flr-4 Sch-E HPlcmt-west ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-RearStorageFlr4 Sys-4 Flr-3 Sch-E HPlcmt-west ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-RestroomFlr1 Sys-3 Flr-2 Sch-F HPlcmt-north ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 351 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:Water | Autosized | gal/min | Plant Loop | Chilled Water Loop | ||
| OS:Coil:Heating:Water | Autosized | gal/min | Plant Loop | Hot Water Loop | ||
| OS:Fan:VariableVolume | Autosized | cfm | Pressure Rise | 5.85 | inH_{2}O | |
| OS:SetpointManager:Scheduled | Control Variable - Temperature | 55.4 to 55.4 | F | |||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 1,755 | ft^2 | 2 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:VAV:Reheat | 2 | ||||
(controls) |
||||||
| HVAC Operation Schedule | VAV with Reheat Occ Sch | |||||
| Night Cycle Setting | CycleOnAny | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
Plant Loops Detail
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:Pump:ConstantSpeed | Autosized | gal/min | Rated Power Consumption | Autosized | W | |
| OS:Chiller:Electric:EIR | 27,465.10 | Btu/h | Reference COP | 4.50 | ||
| OS:Chiller:Electric:EIR (cont) | Chiller Source | Condenser Water Loop | ||||
| OS:SetpointManager:Scheduled | Control Variable - Temperature | 44.6 to 44.6 | F | |||
| OS:Chiller:Electric:EIR | 0.00 | Btu/h | Reference COP | 4.50 | ||
| OS:Chiller:Electric:EIR (cont) | Chiller Source | Condenser Water Loop | ||||
(demand) |
||||||
| OS:Coil:Cooling:Water | Air Loop | VAV with Reheat | ||||
(controls) |
||||||
| Loop Flow Rate Range | Autosized | gal/min | Minimum Loop Flow Rate | 0.0 | gal/min | |
| Loop Temperature Range | 32.0 to 212.0 | F | ||||
| Design Loop Exit Temperature | 44.60 | F | ||||
| Loop Design Temperature Difference | 10.80 | R |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:Pump:ConstantSpeed | Autosized | gal/min | Rated Power Consumption | Autosized | W | |
| OS:CoolingTower:SingleSpeed - Air | Autosized | gal/min | ||||
| OS:CoolingTower:SingleSpeed (cont) - Water | Autosized | cfm | Fan Power at Design Air Flow Rate | 312,640.91 | W | |
| OS:SetpointManager:Scheduled | Control Variable - Temperature | 84.2 to 84.2 | F | |||
(demand) |
||||||
| OS:Chiller:Electric:EIR | Plant Loop | Chilled Water Loop | ||||
| OS:Chiller:Electric:EIR | Plant Loop | Chilled Water Loop | ||||
(controls) |
||||||
| Loop Flow Rate Range | Autosized | gal/min | Minimum Loop Flow Rate | 0.0 | gal/min | |
| Loop Temperature Range | 32.0 to 212.0 | F | ||||
| Design Loop Exit Temperature | 84.20 | F | ||||
| Loop Design Temperature Difference | 10.80 | R |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:Pump:VariableSpeed | Autosized | gal/min | Rated Power Consumption | Autosized | W | |
| OS:Boiler:HotWater | 323,767.46 | Btu/h | Nominal Thermal Efficiency | 0.83 | fraction | |
| OS:SetpointManager:OutdoorAirReset | ||||||
| OS:Boiler:HotWater | 323,767.46 | Btu/h | Nominal Thermal Efficiency | 0.83 | fraction | |
(demand) |
||||||
| OS:Coil:Heating:Water | Air Loop | Make-up air unit | ||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 1 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 2 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 3 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 4 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 5 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 6 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 7 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 8 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 9 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 10 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 11 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 12 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 13 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 14 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 15 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 16 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 17 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 18 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 19 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 20 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 21 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 22 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 23 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 24 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 25 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 26 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 27 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 28 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 29 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 30 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 31 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 32 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 33 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 34 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 35 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 36 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 37 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 38 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 39 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 40 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 41 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 42 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 43 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 44 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 45 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 46 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 47 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 48 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 49 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 50 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 51 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 52 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 53 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 54 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 55 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 56 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 57 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 58 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 59 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 60 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 61 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 62 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 63 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 64 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 65 | |||||
| OS:Coil:Heating:Water | Air Loop | VAV with Reheat | ||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 66 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 67 | |||||
| Air Terminal Connections | 2 | |||||
(controls) |
||||||
| Loop Flow Rate Range | Autosized | gal/min | Minimum Loop Flow Rate | 0.0 | gal/min | |
| Loop Temperature Range | 32.0 to 212.0 | F | ||||
| Design Loop Exit Temperature | 179.60 | F | ||||
| Loop Design Temperature Difference | 28.80 | R |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:Pump:ConstantSpeed | Autosized | gal/min | Rated Power Consumption | Autosized | W | |
| OS:WaterHeater:Mixed | 300 | gal | Heater Thermal Efficiency | 0.81 | fraction | |
| OS:SetpointManager:Scheduled | Control Variable - Temperature | 140.0 to 140.0 | F | |||
(demand) |
||||||
| OS:WaterUse:Connections | Water Use Connections 1 | |||||
| OS:WaterUse:Connections | Water Use Connections 2 | |||||
| OS:WaterUse:Connections | Water Use Connections 3 | |||||
| OS:WaterUse:Connections | Water Use Connections 4 | |||||
| OS:WaterUse:Connections | Water Use Connections 5 | |||||
| OS:WaterUse:Connections | Water Use Connections 6 | |||||
| OS:WaterUse:Connections | Water Use Connections 7 | |||||
| OS:WaterUse:Connections | Water Use Connections 8 | |||||
| OS:WaterUse:Connections | Water Use Connections 9 | |||||
| OS:WaterUse:Connections | Water Use Connections 10 | |||||
| OS:WaterUse:Connections | Water Use Connections 11 | |||||
| OS:WaterUse:Connections | Water Use Connections 12 | |||||
| OS:WaterUse:Connections | Water Use Connections 13 | |||||
| OS:WaterUse:Connections | Water Use Connections 14 | |||||
| OS:WaterUse:Connections | Water Use Connections 15 | |||||
| OS:WaterUse:Connections | Water Use Connections 16 | |||||
| OS:WaterUse:Connections | Water Use Connections 17 | |||||
| OS:WaterUse:Connections | Water Use Connections 18 | |||||
| OS:WaterUse:Connections | Water Use Connections 19 | |||||
| OS:WaterUse:Connections | Water Use Connections 20 | |||||
| OS:WaterUse:Connections | Water Use Connections 21 | |||||
| OS:WaterUse:Connections | Water Use Connections 22 | |||||
| OS:WaterUse:Connections | Water Use Connections 23 | |||||
| OS:WaterUse:Connections | Water Use Connections 24 | |||||
| OS:WaterUse:Connections | Water Use Connections 25 | |||||
| OS:WaterUse:Connections | Water Use Connections 26 | |||||
| OS:WaterUse:Connections | Water Use Connections 27 | |||||
| OS:WaterUse:Connections | Water Use Connections 28 | |||||
| OS:WaterUse:Connections | Water Use Connections 29 | |||||
| OS:WaterUse:Connections | Water Use Connections 30 | |||||
| OS:WaterUse:Connections | Water Use Connections 31 | |||||
| OS:WaterUse:Connections | Water Use Connections 32 | |||||
| OS:WaterUse:Connections | Water Use Connections 33 | |||||
| OS:WaterUse:Connections | Water Use Connections 34 | |||||
| OS:WaterUse:Connections | Water Use Connections 35 | |||||
| OS:WaterUse:Connections | Water Use Connections 36 | |||||
| OS:WaterUse:Connections | Water Use Connections 37 | |||||
| OS:WaterUse:Connections | Water Use Connections 38 | |||||
| OS:WaterUse:Connections | Water Use Connections 39 | |||||
| OS:WaterUse:Connections | Water Use Connections 40 | |||||
| OS:WaterUse:Connections | Water Use Connections 41 | |||||
| OS:WaterUse:Connections | Water Use Connections 42 | |||||
| OS:WaterUse:Connections | Water Use Connections 43 | |||||
| OS:WaterUse:Connections | Water Use Connections 44 | |||||
| OS:WaterUse:Connections | Water Use Connections 45 | |||||
| OS:WaterUse:Connections | Water Use Connections 46 | |||||
| OS:WaterUse:Connections | Water Use Connections 47 | |||||
| OS:WaterUse:Connections | Water Use Connections 48 | |||||
(controls) |
||||||
| Loop Flow Rate Range | Autosized | gal/min | Minimum Loop Flow Rate | 0.0 | gal/min | |
| Loop Temperature Range | 50.0 to 140.0 | F | ||||
| Design Loop Exit Temperature | 140.00 | F | ||||
| Loop Design Temperature Difference | 9.00 | R |
Outdoor Air
| Average Number of Occupants | Nominal Number of Occupants | Zone Volume (ft^3) | Avg. Mechanical Ventilation (ach) | Min. Mechanical Ventilation (ach) | Avg. Infiltration (ach) | Min. Infiltration (ach) | Avg. Simple Ventilation (ach) | Min. Simple Ventilation (ach) | |
|---|---|---|---|---|---|---|---|---|---|
| SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.86 | 1.51 | 17820 | 0.332 | 0.32 | 0.018 | 0.0 | 0.0 | 0.0 |
| SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.72 | 1.26 | 12150 | 0.439 | 0.393 | 0.018 | 0.0 | 0.0 | 0.0 |
| SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.72 | 1.26 | 12150 | 0.439 | 0.393 | 0.02 | 0.0 | 0.0 | 0.0 |
| SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.72 | 1.26 | 12150 | 0.424 | 0.389 | 0.17 | 0.0 | 0.0 | 0.0 |
| SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | 0.75 | 1.5 | 1782 | 4.479 | 4.343 | 0.038 | 0.0 | 0.0 | 0.0 |
| SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | 0.75 | 1.5 | 1458 | 5.473 | 5.308 | 0.048 | 0.0 | 0.0 | 0.0 |
| SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | 0.75 | 1.5 | 1458 | 5.473 | 5.308 | 0.053 | 0.0 | 0.0 | 0.0 |
| SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | 0.75 | 1.5 | 1458 | 5.474 | 5.308 | 0.227 | 0.0 | 0.0 | 0.0 |
| SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | 1.56 | 3.26 | 3861 | 1.026 | 0.99 | 0.035 | 0.0 | 0.0 | 0.0 |
| SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | 3.12 | 6.52 | 3861 | 1.151 | 0.0 | 0.035 | 0.0 | 0.0 | 0.0 |
| SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | 14.67 | 16.31 | 19307 | 1.578 | 1.52 | 0.047 | 0.0 | 0.0 | 0.0 |
| SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | 3.51 | 6.53 | 15444 | 0.717 | 0.0 | 0.037 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN | 0.06 | 0.1 | 2376 | 0.331 | 0.318 | 0.145 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN | 0.06 | 0.1 | 1944 | 0.405 | 0.389 | 0.183 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN | 0.06 | 0.1 | 1944 | 0.405 | 0.389 | 0.202 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN | 0.06 | 0.1 | 1944 | 0.405 | 0.388 | 0.365 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 0.08 | 0.13 | 1485 | 0.388 | 0.375 | 0.04 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | 0.08 | 0.13 | 1215 | 0.474 | 0.458 | 0.05 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | 0.08 | 0.13 | 1215 | 0.474 | 0.458 | 0.055 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | 0.08 | 0.13 | 1215 | 0.474 | 0.459 | 0.238 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.75 | 1.31 | 3861 | 0.669 | 0.589 | 0.033 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.75 | 1.31 | 3861 | 0.668 | 0.589 | 0.033 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.75 | 1.31 | 3861 | 0.66 | 0.588 | 0.033 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3861 | 0.689 | 0.59 | 0.033 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3861 | 0.687 | 0.591 | 0.033 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | 0.75 | 1.31 | 3159 | 0.831 | 0.718 | 0.129 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 3.0 | 5.22 | 12637 | 0.853 | 0.722 | 0.042 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 2.42 | 4.22 | 10207 | 0.841 | 0.721 | 0.042 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 3.0 | 5.22 | 12637 | 0.839 | 0.721 | 0.042 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0.75 | 1.31 | 3159 | 0.827 | 0.72 | 0.042 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.866 | 0.723 | 0.042 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 3.0 | 5.22 | 12636 | 0.866 | 0.723 | 0.042 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.832 | 0.722 | 0.042 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 3.0 | 5.22 | 12636 | 0.881 | 0.724 | 0.042 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.872 | 0.723 | 0.042 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | 0.75 | 1.31 | 3159 | 0.804 | 0.717 | 0.142 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 3.0 | 5.22 | 12637 | 0.841 | 0.721 | 0.046 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 2.42 | 4.22 | 10207 | 0.84 | 0.72 | 0.046 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 3.0 | 5.22 | 12637 | 0.838 | 0.721 | 0.046 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0.75 | 1.31 | 3159 | 0.826 | 0.719 | 0.046 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.862 | 0.722 | 0.046 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 3.0 | 5.22 | 12636 | 0.874 | 0.723 | 0.046 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.835 | 0.722 | 0.046 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 3.0 | 5.22 | 12636 | 0.878 | 0.723 | 0.046 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.866 | 0.722 | 0.046 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | 0.75 | 1.31 | 3159 | 0.778 | 0.713 | 0.301 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 3.0 | 5.22 | 12637 | 0.801 | 0.713 | 0.198 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 2.42 | 4.22 | 10207 | 0.8 | 0.713 | 0.198 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 3.0 | 5.22 | 12637 | 0.8 | 0.713 | 0.198 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 0.75 | 1.31 | 3159 | 0.788 | 0.713 | 0.198 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.813 | 0.714 | 0.198 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 3.0 | 5.22 | 12636 | 0.822 | 0.714 | 0.198 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.805 | 0.714 | 0.198 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 3.0 | 5.22 | 12636 | 0.823 | 0.714 | 0.198 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.816 | 0.714 | 0.198 | 0.0 | 0.0 | 0.0 |
| SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 0.62 | 0.98 | 11583 | 0.388 | 0.374 | 0.04 | 0.0 | 0.0 | 0.0 |
| SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.09 | 0.16 | 3861 | 0.332 | 0.32 | 0.033 | 0.0 | 0.0 | 0.0 |
| SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.23 | 0.4 | 9505 | 0.332 | 0.319 | 0.033 | 0.0 | 0.0 | 0.0 |
| SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN | 0.06 | 0.1 | 2377 | 0.339 | 0.319 | 0.145 | 0.0 | 0.0 | 0.0 |
| SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN | 0.06 | 0.1 | 1944 | 0.414 | 0.391 | 0.183 | 0.0 | 0.0 | 0.0 |
| SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN | 0.06 | 0.1 | 1944 | 0.415 | 0.39 | 0.202 | 0.0 | 0.0 | 0.0 |
| SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN | 0.06 | 0.1 | 1944 | 0.437 | 0.389 | 0.365 | 0.0 | 0.0 | 0.0 |
| SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | 0.13 | 0.2 | 2377 | 0.388 | 0.375 | 0.174 | 0.0 | 0.0 | 0.0 |
| SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | 0.13 | 0.2 | 1945 | 0.474 | 0.459 | 0.219 | 0.0 | 0.0 | 0.0 |
| SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | 0.13 | 0.2 | 1945 | 0.474 | 0.459 | 0.242 | 0.0 | 0.0 | 0.0 |
| SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | 0.13 | 0.2 | 1945 | 0.474 | 0.46 | 0.438 | 0.0 | 0.0 | 0.0 |
| SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.62 | 1.09 | 3861 | 0.332 | 0.32 | 0.033 | 0.0 | 0.0 | 0.0 |
Cash Flow
No Data to Show for Cash Flow
Site and Source Summary
| Total Energy (kBtu) | Energy Per Total Building Area (kBtu/ft^2) | Energy Per Conditioned Building Area (kBtu/ft^2) | |
|---|---|---|---|
| Total Site Energy | 2731722.8 | 63.2 | 63.2 |
| Net Site Energy | 2731722.8 | 63.2 | 63.2 |
| Total Source Energy | 4430978.9 | 102.6 | 102.6 |
| Net Source Energy | 4430978.9 | 102.6 | 102.6 |
| Site=>Source Conversion Factor | |
|---|---|
| Electricity | 3.167 |
| Natural Gas | 1.084 |
| District Cooling | 1.056 |
| District Heating | 3.613 |
Schedule Overview
| Schedule | Type Limits | Rules | Use Count |
|---|---|---|---|
| Air Velocity Schedule | Velocity | 0 | 11 |
| Always On | Dimensionless | 0 | 67 |
| CHW Temp | Temperature | 3 | 1 |
| Clothing Schedule | ClothingInsulation | 1 | 11 |
| CW Temp | Temperature | 3 | 1 |
| Make-up air unit Occ Sch | Dimensionless | 7 | 2 |
| Makeup-Air Unit Supply Air Temp | Temperature | 0 | 1 |
| NECB-A-Electric-Equipment | Dimensionless | 3 | 1 |
| NECB-A-Lighting | Dimensionless | 3 | 1 |
| NECB-A-Occupancy | Dimensionless | 3 | 1 |
| NECB-A-Service Water Heating | Dimensionless | 3 | 1 |
| NECB-A-Thermostat Setpoint-Cooling | Temperature | 3 | 3 |
| NECB-A-Thermostat Setpoint-Heating | Temperature | 3 | 3 |
| NECB-Activity | ActivityLevel | 0 | 67 |
| NECB-B-Electric-Equipment | Dimensionless | 3 | 2 |
| NECB-B-Lighting | Dimensionless | 3 | 2 |
| NECB-B-Occupancy | Dimensionless | 3 | 2 |
| NECB-B-Service Water Heating | Dimensionless | 3 | 2 |
| NECB-B-Thermostat Setpoint-Cooling | Temperature | 3 | 6 |
| NECB-B-Thermostat Setpoint-Heating | Temperature | 3 | 6 |
| NECB-C-Electric-Equipment | Dimensionless | 3 | 4 |
| NECB-C-Lighting | Dimensionless | 3 | 4 |
| NECB-C-Occupancy | Dimensionless | 3 | 4 |
| NECB-C-Thermostat Setpoint-Cooling | Temperature | 3 | 9 |
| NECB-C-Thermostat Setpoint-Heating | Temperature | 3 | 9 |
| NECB-E-Electric-Equipment | Dimensionless | 3 | 9 |
| NECB-E-Lighting | Dimensionless | 3 | 9 |
| NECB-E-Occupancy | Dimensionless | 3 | 9 |
| NECB-E-Service Water Heating | Dimensionless | 3 | 9 |
| NECB-E-Thermostat Setpoint-Cooling | Temperature | 3 | 19 |
| NECB-E-Thermostat Setpoint-Heating | Temperature | 3 | 19 |
| NECB-F-Electric-Equipment | Dimensionless | 3 | 50 |
| NECB-F-Lighting | Dimensionless | 3 | 50 |
| NECB-F-Occupancy | Dimensionless | 3 | 50 |
| NECB-F-Service Water Heating | Dimensionless | 3 | 35 |
| NECB-F-Thermostat Setpoint-Cooling | Temperature | 3 | 105 |
| NECB-F-Thermostat Setpoint-Heating | Temperature | 3 | 105 |
| NECB-H-Electric-Equipment | Dimensionless | 3 | 1 |
| NECB-H-Lighting | Dimensionless | 3 | 1 |
| NECB-H-Occupancy | Dimensionless | 3 | 1 |
| NECB-H-Service Water Heating | Dimensionless | 3 | 1 |
| NECB-H-Thermostat Setpoint-Cooling | Temperature | 3 | 3 |
| NECB-H-Thermostat Setpoint-Heating | Temperature | 3 | 3 |
| ON_OFF_ALWAYS_OFF | Availability | 3 | 42 |
| Schedule Ruleset 10 | 0 | 1 | |
| Schedule Ruleset 100 | 0 | 1 | |
| Schedule Ruleset 101 | 0 | 1 | |
| Schedule Ruleset 102 | 0 | 1 | |
| Schedule Ruleset 103 | 0 | 1 | |
| Schedule Ruleset 104 | 0 | 1 | |
| Schedule Ruleset 105 | 0 | 1 | |
| Schedule Ruleset 106 | 0 | 1 | |
| Schedule Ruleset 107 | 0 | 1 | |
| Schedule Ruleset 108 | 0 | 1 | |
| Schedule Ruleset 109 | 0 | 1 | |
| Schedule Ruleset 11 | 0 | 1 | |
| Schedule Ruleset 110 | 0 | 1 | |
| Schedule Ruleset 111 | 0 | 1 | |
| Schedule Ruleset 112 | 0 | 1 | |
| Schedule Ruleset 113 | 0 | 1 | |
| Schedule Ruleset 114 | 0 | 1 | |
| Schedule Ruleset 115 | 0 | 1 | |
| Schedule Ruleset 116 | 0 | 1 | |
| Schedule Ruleset 117 | 0 | 1 | |
| Schedule Ruleset 118 | 0 | 1 | |
| Schedule Ruleset 119 | 0 | 1 | |
| Schedule Ruleset 12 | 0 | 1 | |
| Schedule Ruleset 120 | 0 | 1 | |
| Schedule Ruleset 121 | 0 | 1 | |
| Schedule Ruleset 122 | 0 | 1 | |
| Schedule Ruleset 123 | 0 | 1 | |
| Schedule Ruleset 124 | 0 | 1 | |
| Schedule Ruleset 125 | 0 | 1 | |
| Schedule Ruleset 126 | 0 | 1 | |
| Schedule Ruleset 127 | 0 | 1 | |
| Schedule Ruleset 128 | 0 | 1 | |
| Schedule Ruleset 129 | 0 | 1 | |
| Schedule Ruleset 13 | 0 | 1 | |
| Schedule Ruleset 130 | 0 | 1 | |
| Schedule Ruleset 131 | 0 | 1 | |
| Schedule Ruleset 132 | 0 | 1 | |
| Schedule Ruleset 133 | 0 | 1 | |
| Schedule Ruleset 134 | 0 | 1 | |
| Schedule Ruleset 135 | 0 | 1 | |
| Schedule Ruleset 136 | 0 | 1 | |
| Schedule Ruleset 137 | 0 | 1 | |
| Schedule Ruleset 138 | 0 | 1 | |
| Schedule Ruleset 139 | 0 | 1 | |
| Schedule Ruleset 14 | 0 | 1 | |
| Schedule Ruleset 140 | 0 | 1 | |
| Schedule Ruleset 141 | 0 | 1 | |
| Schedule Ruleset 142 | 0 | 1 | |
| Schedule Ruleset 143 | 0 | 1 | |
| Schedule Ruleset 144 | 0 | 1 | |
| Schedule Ruleset 145 | 0 | 1 | |
| Schedule Ruleset 146 | 0 | 1 | |
| Schedule Ruleset 15 | 0 | 1 | |
| Schedule Ruleset 16 | 0 | 1 | |
| Schedule Ruleset 17 | 0 | 1 | |
| Schedule Ruleset 18 | 0 | 1 | |
| Schedule Ruleset 19 | 0 | 1 | |
| Schedule Ruleset 20 | 0 | 1 | |
| Schedule Ruleset 21 | 0 | 1 | |
| Schedule Ruleset 22 | 0 | 1 | |
| Schedule Ruleset 23 | 0 | 1 | |
| Schedule Ruleset 24 | 0 | 1 | |
| Schedule Ruleset 25 | 0 | 1 | |
| Schedule Ruleset 26 | 0 | 1 | |
| Schedule Ruleset 27 | 0 | 1 | |
| Schedule Ruleset 28 | 0 | 1 | |
| Schedule Ruleset 29 | 0 | 1 | |
| Schedule Ruleset 3 | 0 | 1 | |
| Schedule Ruleset 30 | 0 | 1 | |
| Schedule Ruleset 31 | 0 | 1 | |
| Schedule Ruleset 32 | 0 | 1 | |
| Schedule Ruleset 33 | 0 | 1 | |
| Schedule Ruleset 34 | 0 | 1 | |
| Schedule Ruleset 35 | 0 | 1 | |
| Schedule Ruleset 36 | 0 | 1 | |
| Schedule Ruleset 37 | 0 | 1 | |
| Schedule Ruleset 38 | 0 | 1 | |
| Schedule Ruleset 39 | 0 | 1 | |
| Schedule Ruleset 4 | 0 | 1 | |
| Schedule Ruleset 40 | 0 | 1 | |
| Schedule Ruleset 41 | 0 | 1 | |
| Schedule Ruleset 42 | 0 | 1 | |
| Schedule Ruleset 43 | 0 | 1 | |
| Schedule Ruleset 44 | 0 | 1 | |
| Schedule Ruleset 45 | 0 | 1 | |
| Schedule Ruleset 46 | 0 | 1 | |
| Schedule Ruleset 47 | 0 | 1 | |
| Schedule Ruleset 48 | 0 | 1 | |
| Schedule Ruleset 49 | 0 | 1 | |
| Schedule Ruleset 5 | 0 | 1 | |
| Schedule Ruleset 50 | 0 | 1 | |
| Schedule Ruleset 51 | 0 | 1 | |
| Schedule Ruleset 52 | 0 | 1 | |
| Schedule Ruleset 53 | 0 | 1 | |
| Schedule Ruleset 54 | 0 | 1 | |
| Schedule Ruleset 55 | 0 | 1 | |
| Schedule Ruleset 56 | 0 | 1 | |
| Schedule Ruleset 57 | 0 | 1 | |
| Schedule Ruleset 58 | 0 | 1 | |
| Schedule Ruleset 59 | 0 | 1 | |
| Schedule Ruleset 6 | 0 | 1 | |
| Schedule Ruleset 60 | 0 | 1 | |
| Schedule Ruleset 61 | 0 | 1 | |
| Schedule Ruleset 62 | 0 | 1 | |
| Schedule Ruleset 63 | 0 | 1 | |
| Schedule Ruleset 64 | 0 | 1 | |
| Schedule Ruleset 65 | 0 | 1 | |
| Schedule Ruleset 66 | 0 | 1 | |
| Schedule Ruleset 67 | 0 | 1 | |
| Schedule Ruleset 68 | 0 | 1 | |
| Schedule Ruleset 69 | 0 | 1 | |
| Schedule Ruleset 7 | 0 | 1 | |
| Schedule Ruleset 70 | 0 | 1 | |
| Schedule Ruleset 71 | 0 | 1 | |
| Schedule Ruleset 72 | 0 | 1 | |
| Schedule Ruleset 73 | 0 | 1 | |
| Schedule Ruleset 74 | 0 | 1 | |
| Schedule Ruleset 75 | 0 | 1 | |
| Schedule Ruleset 76 | 0 | 1 | |
| Schedule Ruleset 77 | 0 | 1 | |
| Schedule Ruleset 78 | 0 | 1 | |
| Schedule Ruleset 79 | 0 | 1 | |
| Schedule Ruleset 8 | 0 | 1 | |
| Schedule Ruleset 80 | 0 | 1 | |
| Schedule Ruleset 81 | 0 | 1 | |
| Schedule Ruleset 82 | 0 | 1 | |
| Schedule Ruleset 83 | 0 | 1 | |
| Schedule Ruleset 84 | 0 | 1 | |
| Schedule Ruleset 85 | 0 | 1 | |
| Schedule Ruleset 86 | 0 | 1 | |
| Schedule Ruleset 87 | 0 | 1 | |
| Schedule Ruleset 88 | 0 | 1 | |
| Schedule Ruleset 89 | 0 | 1 | |
| Schedule Ruleset 9 | 0 | 1 | |
| Schedule Ruleset 90 | 0 | 1 | |
| Schedule Ruleset 91 | 0 | 1 | |
| Schedule Ruleset 92 | 0 | 1 | |
| Schedule Ruleset 93 | 0 | 1 | |
| Schedule Ruleset 94 | 0 | 1 | |
| Schedule Ruleset 95 | 0 | 1 | |
| Schedule Ruleset 96 | 0 | 1 | |
| Schedule Ruleset 97 | 0 | 1 | |
| Schedule Ruleset 98 | 0 | 1 | |
| Schedule Ruleset 99 | 0 | 1 | |
| Service Water Loop Temp - 140F | Temperature | 0 | 2 |
| Supply Air Temp | Temperature | 0 | 1 |
| VAV with Reheat Occ Sch | Dimensionless | 7 | 2 |
| Water Heater Ambient Temp Schedule - 70F | Temperature | 0 | 1 |
| Work Efficiency Schedule | Dimensionless | 0 | 11 |